Technical Data
Technical data TBEN-S1-4DXP
230
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
14.7
Technical data TBEN-S1-4DXP
The device has four DXP channels. Up to four 3-wire PNP sensors or four PNP DC actuators can
be connected.
Technical data
Supply
Operating current (from V1)
< 150 mA
Sensor/actuator supply VAUX1
Supply connector C0…C1 from V1
short-circuit proof, 0.5 A per port
Sensor/actuator supply VAUX2
Supply connector C2…C3 from V2
short-circuit proof, 0.5 A per port
Potential isolation
From V1 and V2 voltage group,
voltages up to 500 VDC
Total current
Total current max. 4 A per voltage group
Total current V1 + V2 max. 5.5 A at 70°C per
module
Digital inputs
Number of channels
4
Connection technology
M8, 3-pole
Input type
EN 61131-2 type 3, PNP
Type of input diagnostics
Group diagnostics
Signal voltage low level
< 5 V
Signal voltage high level
> 11 V
Signal current low level
< 1.5 mA
Signal current high level
> 2 mA
Input resistance low level
Min. 3.33 kΩ
Input resistance high level
Max. 5.5 kΩ
Input delay
0.2 ms/3 ms
Input frequency
400 Hz
Potential isolation
Galvanic isolation to P1/P2,
voltage proof up to 500 VDC
Digital outputs
Number of channels
4
Connection technology
M8, 3-pole
Output type
PNP
Type of output diagnostics
Channel diagnostics
Output voltage
24 VDC from potential group
Output current per channel
2 A, short-circuit-proof
Load type
EN 60947-5-1: DC-13
Load type (UL condition)
Resistive, pilot duty
Short-circuit protection
Yes
Potential isolation
Galvanic isolation to P1/P2,
voltage proof up to 500 VDC
General information
MTTF
307 years acc. to SN 29500 (Ed. 99) 20 °C