Parameterizing and Configuring
Configuring the devices at EtherNet/IP
154
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Class 157 (0x9D) – Ext. Function Digital
This class data and parameters for the extended digital functions (counter).
Applies to:
n
TBEN-S1-8DIP
n
TBEN-S1-8DIP-D
n
TBEN-S1-4DIP-4DOP
n
TBEN-S1-4DXP
n
TBEN-S1-8DXP
n
TBEN-S2-8DIP
n
TBEN-S2-8DXP
Attribute no.
Designation
Get/set
Type
Meaning
Dec.
Hex.
Parameters
1
0x01
Extended digital function
CNT
G/S
USINT
0: deactivated
1: Input filter and pulse
stretch
2: reserved
3: reserved
4: Counter
2
0x02
Input filter
G/S
USINT
0: 0.2 ms
1: 3 ms
3
0x03
Pulse stretching input (*10
ms)
G/S
USINT
4
0x04
Counter value
G
UDINT
5
0x05
Counter frequency (hz)
G
UINT
6
0x06
Status
G
USINT
7
0x07
Counter reset
G
USINT
0: inactive
1: active