V04.00 | 2021/05
161
Class 170 (0xAA) – VAUX Control
This class contains parameters for of the 24 VDC sensor/ actuator supply.
Applies to:
n
TBEN-S2-8DXP
Attr. no.
Designation
Get/Set
Type
Meaning
Dec.
Hex.
Parameters
1
0x01
VAUX1 pin1 C0 (Ch0/1)
G/S
USINT
0: 24 VDC
1: switchable
2: off
2
0x02
VAUX1 pin1 C1 (Ch2/3)
G/S
USINT
0: 24 VDC
1: switchable
2: off
3
0x03
VAUX1 pin1 C2 (Ch4/5)
G/S
USINT
0: 24 VDC
1: switchable
2: off
4
0x04
VAUX1 pin1 C3 (Ch6/7)
G/S
USINT
0: 24 VDC
1: switchable
2: off
5
0x05
VAUX1 pin1 C0 (Ch0/1)
G
USINT
0: on
1: off
6
0x06
VAUX1 Pin1 C1 (Ch2/3)
G
USINT
0: on
1: off
7
0x07
VAUX1 pin1 C2 (Ch4/5)
G
USINT
0: on
1: off
8
0x08
VAUX2 Pin1 C0 (ch0/1)
G
USINT
0: on
1: off