Measurement value representation of analog modules
9.3.1
Measurement value representation – TBEN-S2-4AI
Voltage – standard
-10…10 V
Diagnostics
decimal
hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 3.052 × 10
-4
) V
> 10.1000 V
"Upper limit value exceeded” ON
32767
7FFF
< 10.0500 V
"Upper limit value exceeded" OFF
32767
7FFF
10.0000 V
Nominal range
32767
7FFF
9.991 V
32736
7FE0
0.005 V
16
0010
0 V
0
0000
-0.0050 V
-16
FFF0
-9.995 V
-32752
8010
-9.999 V
-32767
8001
-10.0000 V
-32768
8000
> -10.0500 V
"Lower limit value underrun" OFF
-32768
8000
> -10.1000 V
"Lower limit value underrun" ON
-32768
8000
0…10 V
Diagnostics
decimal
hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 3.052 × 10
-4
) V
> 10.1000 V
"Upper limit value exceeded” ON
32767
7FFF
< 10.0500 V
"Upper limit value exceeded" OFF
32767
7FFF
10.0000 V
Nominal range
32767
7FFF
9.991 V
32736
7FE0
0.005 V
16
0010
0 V
0
0000
> -0.0500 V
"Lower limit value underrun" OFF
0
0000
> -0.10000 V
"Lower limit value underrun" ON
0
0000