Parameterizing and Configuring
Configuring the devices at EtherNet/IP
156
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Class 160 (0xA0) – Ext. Function Digital
This class data and parameters for the extended digital functions (PWM).
Applies to:
n
TBEN-S1-8DXP
n
TBEN-S2-8DXP
Attribute no.
Designation
Get/Set
Type
Meaning
Dec.
Hex.
Parameters
1
0x01
Extended digital function PWM
G/S
USINT
0: deactivated
1: reserved
2
0x02
Input filter
G/S
USINT
0: 0.2 ms
1: 3 ms
3
0x03
Pulse stretching input (*10 ms)
G/S
USINT
4
0x04
Overcurrent PWM output
G
USINT
0: -
1: active
5
0x05
Overcurrent PWM output
G
USINT
0: -
1: active
6
0x06
Duty Cycle
G
USINT