Operating
Evaluating diagnostic data
178
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
TBEN-S1-8DXP – diagnostic data mapping
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
n
-
-
-
-
-
-
VERR V2
ch4-7
VERR V1
ch0-3
n + 1
ERR7
ERR6
ERR5
ERR4
ERR3
ERR2
ERR1
ERR0
PROFINET error codes
Station diagnostics (slot 0)
PROFINET diagnostics
Diagnostics
Error code
Channel
Undervoltage
V1
0x0002
0
V2
0x0002
1
I/O diagnostics (slot 1)
PROFINET diagnostics
Diagnostics
Connector/pin
Error code
Channel
Overcurrent supply group
Overcurrent supply VAUX1 at channel 0…3
VERR V1 Ch 0-3
C0
0x0120
0
C1
C2
C3
Overcurrent supply group
Overcurrent supply VAUX2 at channel 4…7
VERR V2 Ch 4-7
C4
0x0121
0
C5
C6
C7
Short-circuit at output
Overcurrent
ERR0
C0
0x0001
0
ERR1
C1
0x0001
1
ERR2
C2
0x0001
2
ERR3
C3
0x0001
3
ERR4
C4
0x0001
4
ERR5
C5
0x0001
5
ERR6
C6
0x0001
6
ERR7
C7
0x0001
7