V04.00 | 2021/05
145
Attribute no.
Designation
Get/Set
Type
Meaning
Dec.
Hex.
12
0x0C
Data
representation
G/S
USINT
0: Standard
1: NE43
2: Extended range
13
0x0D
Temperature
unit
G/S
USINT
0: Celsius
1: Fahrenheit
14
0x0E
Input averaging
filter DIFT
G/S
USINT
0 = standard
1 = smooth
2 = fast
3: off
15
0x0F
Deactivate
channel
G/S
USINT
0 = no
1 = yes
16
0x10
Deactivate
diagnostics
G/S
USINT
0 = no
1 = yes
17
0x11
Mains suppres-
sion
G/S
USINT
0: off
1: 50 Hz
2: 60 Hz
18
0x12
Upper limit
value
exceeded
G
USINT
0: -
1: active
19
0x13
Lower limit value
underrun
G
USINT
0: -
1: active
20
0x14
Overflow
G
USINT
0: -
1: active
21
0x15
Underflow
G
USINT
0: -
1: active
22
0x16
Cold junction
error
G
USINT
0: -
1: active
23
0x17
Overcurrent
(RTD only)
G
USINT
0: -
1: active
24
0x18
Wire break
G
USINT
0: -
1: active
25
0x19
Overcurrent
supply VAUX1
G
USINT
0: -
1: active
26
0x1A
Input value
G
UINT