V04.00 | 2021/05
187
2…10 V
Diagnostics
decimal
hexadecimal
(two's complement)
Voltage value U
M
= (dec. Value × 2.8934 × 10
-4
) V + 2 V
> 11.41 V
"Upper limit value exceeded” ON
> 32527
> 7F0F
< 11.28 V
"Upper limit value exceeded" OFF
> 32077
< 7D4D
11.481 V
Nominal range
32767
7FFF
11.407 V
32512
7F00
10 V
27653
6C05
6.741 V
16384
4000
2.000 V
0
0000
> 0.676 V
"Lower limit value underrun" and
"Wire break" OFF
0
0000
< 0.592 V
"Lower limit value underrun" and
"Wire break" ON
0
0000
0…5 V
Diagnostics
decimal
hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 1.808 × 10
-4
) V
> 5.88 V
"Upper limit value exceeded” ON
> 32522
> 7F0A
< 5.80 V
"Upper limit value exceeded" OFF
> 32080
< 7D50
5.926 V
Nominal range
32767
7FFF
5.880 V
32512
7F00
5 V
27655
6C07
2.963 V
16384
4000
0 V
0
0000
> -0.05 V
"Lower limit value underrun" OFF
> -277
> FEEB
< -0.10 V
"Lower limit value underrun" ON
> 553
< FDD7
1…5 V
Diagnostics
decimal
hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 1.4468 × 10
-4
) + 1V
> 5.70 V
"Upper limit value exceeded” ON
> 32485
> 7EE5
< 5.64 V
"Upper limit value exceeded" OFF
> 32071
< 7D47
5.741 V
Nominal range
32767
7FFF
5.704 V
32512
7F00
5 V
27647
6BFF
3.371 V
16384
4000
1.000 V
0
0000
0 V
-6912
E500
> -0.324 V
"Lower limit value underrun" and
"Wire break" OFF
> -4672
> EDC0
< -0.296 V
"Lower limit value underrun" and
"Wire break" ON
> -4865
< ECFF