Operating
Measurement value representation of analog modules
186
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Voltage – extended range
-10…10 V
Diagnostics
decimal
hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 3.617 × 10
-4
) V
> 11.76 V
"Upper limit value exceeded” ON
> 35513
> 7F01
< 11.60 V
"Upper limit value exceeded" OFF
> 32071
< 7D47
11.851 V
Nominal range
32767
7FFF
11.759 V
32512
7F00
10 V
27648
6C00
5.926 V
16384
4000
0 V
0
0000
-1.76 V
-4865
ECFF
-2.500 V
-6912
E500
-5.926 V
-16384
C000
-10 V
-27648
9400
-11.759 V
-32512
8100
-11.851 V
-37768
8000
> -11.60 V
"Lower limit value underrun" OFF
> -32071
> 82B9
> -11.76 V
"Lower limit value underrun" ON
> -35513
< 80FF
0…10 V
Diagnostics
decimal
hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 3.617 × 10
-4
) V
> 11.76 V
"Upper limit value exceeded” ON
> 32513
> 7F01
< 11.60 V
"Upper limit value exceeded" OFF
> 32071
< 7D47
11.851 V
Nominal range
32767
7FFF
11.759 V
32512
7F00
10 V
27648
6C00
5.926 V
16384
4000
0 V
0
0000
> -0.05 V
"Lower limit value underrun" OFF
> -138
> FF76
< -0.10 V
"Lower limit value underrun" ON
> -276
< FEEC