Operating
Measurement value representation of analog modules
216
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Current – NE43
Decimal
hexadecimal
(two's complement)
0…20 mA
Dec. value = 1000 (1/mA) × I
out
(mA)
65535
FFFF
22.000 mA
22001
55F1
22.000 mA
22000
55F0
22.000 mA
21001
5209
21.001 mA
21000
5208
21.000 mA
20001
4E21
20.001 mA
20000
4E20
20.000 mA
8000
1F40
Nominal range
8.000 mA
4000
0FA0
4.000 mA
2
0002
0.002 mA
1
0001
0.001 mA
0
0000
0.000 mA
Decimal
hexadecimal
(two's complement)
4…20 mA
Dec. value = 1000 (1/mA) × I
out
(mA)
65535
FFFF
22.000 mA
22000
> 55F0
22.000 mA
22000
55F0
22.000 mA
21001
5209
21.001 mA
21000
5208
21.000 mA
20001
4E21
20.001 mA
20000
4E20
Nominal range
20.000 mA
8000
1F40
8.000 mA
4000
0FA0
4.000 mA
> 3999
0F9F
≤ 3.999 mA
3800
0ED8
3.800 mA
3600
0E10
3.600 mA
3599
0E0F
3.599 mA
2000
07D0
2.000 mA
> 1999
07CF
1.999 mA
1
0001
0.000 mA