Parameterizing and Configuring
Parameters – overview
40
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Parameters – TBEN-S2-4AI
Parameter name
Value
Meaning
Description
Dec.
Hex.
CWT Current wiring type
0
0x00
Differential
Differential input
1
0x01
Single ended
Connection of sensors with common
ground [
2
0x02
differential without
ground
Differential input
DCH Deactivate channel
0
0x00
No
Channel active
1
0x01
Yes
Channel inactve
DDI
Deactivate
diagnostics
0
0x00
No
Diagnostics active
1
0x01
Yes
Diagnostics inactive
DRE
Data representa-
tion
0
0x00
Standard
1
0x01
NE43
2
0x02
Extended range
INFIL Average value
Cut-off frequency
(at -3 dB)
Cut-off frequency
(at -3 dB)
0
0x00
Standard
5 Hz
2 Hz
1
0x01
smooth
1 Hz
0.25 Hz
2
0x02
fast
30 Hz
15 Hz
3
0x03
Off
250 Hz
125 Hz
IMR
Current range
0
0x00
4…20 mA
1
0x01
0…20 mA
2
0x02
20…20 mA
OPM Operation mode
0
0x00
Thermocouple
Selection of the operation mode for the
respective channel. If a channel is para-
meterized as voltage or current input,
the sensor supply is provided at pin 1
and 3. Thermocouples/RTDs/resistances
must not be connected if the channel is
set to this operation mode.
1
0x01
voltage
2
0x02
Current
3
0x03
Resistance
4
0x04
RTD
RRA
Resistance range
0
0x00
0…100 Ohm
1
0x01
0…400 Ohm
2
0x02
0…2000 Ohm
3
0x03
0…4000 Ohm
RTDT RTD type
0
0x00
Pt100, -200…850 °C, -328…1562 °F
1
0x01
Pt100, -200…150 °C, -328…302 °F
2
0x02
Ni100, -60…250 °C, -76…482 °F
3
0x03
Ni100, -60…150 °C, -76…302 °F
4
0x04
Pt200, -200…850 °C, -328…1562 °F
5
0x05
Pt200, -200…150 °C, -328…302 °F
6
0x06
Pt500, -200…850 °C, -328…1562 °F
7
0x07
Pt500, -200…150 °C, -328…302 °F
8
0x08
Pt1000, -200…850 °C, -328…1562 °F
9
0x09
Pt1000, -200…150 °C, -328…302 °F