V04.00 | 2021/05
195
4…20 mA
Diagnostics
decimal
hexadecimal
(two's complement)
Current value I
M
= (dec. value × 4.883 × 10
-4
) mA
> 20.20 mA
"Upper limit value exceeded” ON
32767
7FFF
< 20.10 mA
"Upper limit value exceeded" OFF
32767
7FFF
20 mA
Nominal range
32767
7FFF
12.00 mA
16384
4000
4 mA
0
0000
> 3.70 mA
"Lower limit value underrun"
and "Underrun" OFF
> -614
> FD9A
< 3.60 mA
"Lower limit value underrun"
and "Underrun" ON
> -819
< FCCD
> 3.00 mA
"Wire break" OFF
> -2048
> F800
< 2.90 mA
"Wire break" ON
> -2253
< F733
-20…20 mA
Diagnostics
decimal
hexadecimal
(two's complement)
Current value I
M
= (dec. value × 6.1037 × 10
-4
) mA
> 20.20 mA
"Upper limit value exceeded” ON
32767
7FFF
< 20.10 mA
"Upper limit value exceeded" OFF
32767
7FFF
20 mA
Nominal range
32767
7FFF
10.00 mA
16384
4000
0 mA
0
0000
-10.00 mA
-16384
C000
-20.00 mA
-32768
8000
> -20.10 mA
"Lower limit value underrun"
and "Underrun" OFF
-32768
8000
< -20.20 mA
"Lower limit value underrun"
and "Underrun" ON
-32768
8000
Current – extended range
0…20 mA
Diagnostics
decimal
hexadecimal
(two's complement)
Current value I
M
= (dec. value × 7.234 × 10
-4
) mA
> 23.519 mA
"Upper limit value exceeded” ON
> 32511
>7EFF
< 23.206 mA
"Upper limit value exceeded" OFF
> 32079
< 7DF4
23.703 mA
Nominal range
32767
7FFF
23.519 mA
32512
7F00
20 mA
27647
6BFF
11.852 mA
16384
4000
0 mA
0
0000
> -0.10 mA
"Lower limit value underrun" OFF
> -138
> FF76
< -0.20 mA
"Lower limit value underrun" ON
> -276
< FEEC