Operating
Evaluating diagnostic data
180
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
TBEN-S2-4AI – diagnostic data mapping
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Channel
0
n
LLVU
UFL
OFL
WBR
V1AOL
ULVE
RTDSC
CJE
Channel
1
n + 1
LLVU
UFL
OFL
WBR
V1AOL
ULVE
RTDSC
CJE
Channel
2
n + 2
LLVU
UFL
OFL
WBR
V1AOL
ULVE
RTDSC
CJE
Channel
3
n + 3
LLVU
UFL
OFL
WBR
V1AOL
ULVE
RTDSC
CJE
PROFINET error codes
Station diagnostics (slot 0)
PROFINET diagnostics
Diagnostics
Error code
Channel
Undervoltage
V1
0x0002
0
V2
0x0002
1
I/O diagnostics (slot 1)
PROFINET diagnostics
Diagnostics
Connector/pin
Error code
Channel
Wire break (WBR)
C0…C3
0x0004
0…3
Overcurrent (RTD
only), (RTDSC)
0x0004
Overcurrent supply
VAUX1 (V1AOL)
0x0004
Upper limit value ex-
ceeded (ULVE)
0x0007
Overflow (OFL)
0x0007
Lower limit value un-
derrun (LLVU)
0x0008
Underflow (UFL)
0x0008
Cold junction error
(CJE)
0x0019