V04.00 | 2021/05
13
4.3.2
Digital modules – extended digital functions
In PROFINET, the extended digital functions are configured via device parameterization via
GSDML file. In EtherNet/IP, the functions are provided in special catalog files for RSLogix from
Rockwell Automation. In Modbus TCP the extended functions are configured via Modbus re-
gisters. In addition to that, the functions are configurable via the device's web server or the
device DTMs.
The digital TBEN modules provide the following extended digital functions:
Digital filter
The function "digital filter" extends the filter time of digital inputs to 3 ms. Digital input signals
can thus be reliably detected even when short-term interfering signals in rough environments
occur.
Impulse stretch
The function "impulse stretch" allows a detection of short signals in longer PLC cycle times by
means of signal extension.
Counter function
A counter is always available on the first input channel.
n
32-bit counter
n
Rotation speed monitoring up to 10 kHz without rotational direction detection
n
Detection of many pulses in short intervals
n
Detection of one track
PWM function
The PWM function is provided at the channels 3 (except for TBEN-Sx-4DIP-4DOP) and 7.
n
Applications: Dimming of indicator lights, LEDs etc.
n
Fix frequency setting of 100 Hz
n
Mark-to-space ratio: 0…100 %
0: off (digital 0)
100: on (digital 1)
n
Operational range: 10…90 %
n
Accuracy (mark-to-space ratio in operational range) 5 %
n
Duty-Cycle (mark-to-space ratio): 0…100 in %,
default 0,
example: 20: Duty cycle 20 to 80 = ratio "on" to "off