Operating
Measurement value representation of analog modules
194
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
-50…50 mV
Diagnostics
decimal
hexadecimal
(two's complement)
Voltage value U
M
= (dec. value × 10
-5
)/2 V
> 0.0550 mV
"Overload/Overcurrent" ON
> 11000
> 2AF8
< 0.0549 mV
"Overload/Overcurrent" OFF
> 10990
< 2AE4
> 0.0525 mV
"Upper limit value exceeded” ON
> 10500
> 2904
< 0.0513 mV
"Upper limit value exceeded" OFF
> 10520
< 280A
0.0500 mV
Nominal range
10000
2710
0.0250 mV
5000
1388
0 mV
0
0000
-0.0250 mV
-5000
EC78
-0.0500 mV
-10000
D8F0
> -0.0513 mV
"Lower limit value underrun"
and "Underrun" OFF
> -10260
> D7F6
< -0.0525 mV
"Lower limit value underrun"
and "Underrun" ON
> -10500
< D6FC
> -0.0549 mV
"Underflow" OFF
> -10980
> D51C
< -0.0550 mV
"Underflow" ON
> -11000
< D508
Current – standard
0…20 mA
Diagnostics
decimal
hexadecimal
(two's complement)
Current value I
M
= (dec. value × 6.104 × 10
-4
) mA
> 20.20 mA
"Upper limit value exceeded” ON
32767
7FFF
< 20.10 mA
"Upper limit value exceeded" OFF
32767
7FFF
20 mA
Nominal range
32767
7FFF
10.00 mA
16384
4000
0 mA
0
0000
> -0.10 mA
"Lower limit value underrun"
and "Underrun" OFF
> -164
> FF5C
< -0.20 mA
"Lower limit value underrun"
and "Underrun" ON
< -328
< FEB8