background image

Assisting the automation

industry since 1986   

User manual

CONTROLLER/DATA RECORDER

MultiCon CMC-99/141

Firmware: 

v.2.27.0

 or higher

Read the user's manual carefully before starting to use the unit or software. 

Producer reserves the right to implement changes without prior notice.

 2016.06.01

MultiCon CMC-99/141_INSSXEN_v.1.17.015 

Summary of Contents for multicon cmc-141

Page 1: ...LLER DATA RECORDER MultiCon CMC 99 141 Firmware v 2 27 0 or higher Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement changes without...

Page 2: ...s General settings 67 7 8 2 Logical channels Hardware input mode 84 7 8 3 Logical Channels Hardware output monitor mode 87 7 8 4 Logical Channels Modbus mode 89 7 8 5 Logical Channels Set point value...

Page 3: ...ules 164 7 11 EXTERNAL OUTPUTS 165 7 11 1 External outputs General settings 165 7 11 2 External outputs Control type as a relay 167 7 11 3 External outputs Control type as a linear output 169 7 11 4 E...

Page 4: ...PPENDICES 234 8 1 PS3 PS4 PS32 PS42 POWER SUPPLY MODULE 234 8 2 UI4 UI8 UI12 U16 U24 I16 I24 VOLTAGE AND CURRENT MEASUREMENT MODULES 235 8 3 UI4N8 UI4D8 UI8N8 UI8D8 MIXED UIN UID MODULES 241 8 4 IS6 I...

Page 5: ...unit must be properly set up according to the application Incorrect configuration can cause defective operation which can lead to unit damage or an accident If in the case of a unit malfunction there...

Page 6: ...asurement visualisation and control of numerous channels This device can operate autonomously or with cooperation with external measurement devices and actuators Essential features of MultiCon CMC 99...

Page 7: ...data sources presentation modes and controlling methods The multi level structure of the MultiCon CMC 99 141 firmware allows for selection of presented data sources presentation modes and controlling...

Page 8: ...lt in physical outputs or virtual outputs which can be used as inputs to logical channels 8 Build in analog input Buid in binary input External input RS 485 Profiles timers Controller Mathematical log...

Page 9: ...net 10M RJ 45 Optional input modules 4 8 16 24x Voltage 0 10V Current 0 20mA 16 24x NTC 0 100k Voltage 0 10V Current 0 20mA Digital TTL HTL 6x Isolated current 4 20mA 4 6x RTD Pt100 Pt500 Pt1000 Cu50...

Page 10: ...nput output terminal 1min 2300V see Fig 4 1 EMC PN EN 61326 1 Weight 340g only base see Fig 4 8 check the current list of measurement modules at producer s website see the full specification in the Ap...

Page 11: ...isolation used with the unit Fig 4 1 meets the expectations and if necessary use appropriate measures of over voltage protection Additionally insure the appropriate air and surface insulation gaps wh...

Page 12: ...ounting hole must be prepared according to Fig 4 2 The thickness of the material of which the panel is made must not exceed 5mm When preparing the mounting hole take the grooves for catches located on...

Page 13: ...LER DATA RECORDER MultiCon CMC 99 141 96 x 96 housing H W 115 mm 144 x 144 housing H W 165 mm Fig 4 3 Minimum distances when assembly of a number of units Fig 4 4 Installing of brackets 13 98 mm 8 mm...

Page 14: ...time delay cut out fuse with a small nominal current value must be used recommended bipolar max 2A and a power supply circuit breaker located near the unit Fig 4 6 In the case of using a monopolar fus...

Page 15: ...pplied To avoid the unit of improper indications keep recommendations listed below Depending on version 85 230 260V AC DC or 19 24 50V DC 16 24 35V AC Fig 4 6 Connection of power supply Avoid running...

Page 16: ...s must be made while power supply is disconnected Fig 4 8 Terminals description The basic performance of the device see Fig 4 8 contains only the extreme left terminals Power supply SERVICE Sensor sup...

Page 17: ...input Slot B RT4 module 4 RTD input Slot C R81 module 8 relay output 1A 250V Slot D ACM module additional serial USB and Ethernet interfaces 4 3 1 Available modules Fig 4 9 Voltage and current input m...

Page 18: ...09 n10 n11 n12 n04 n05 n06 n07 n01 n02 n03 n20 n16 n17 n18 n19 n13 n14 n15 n11 n12 n20 n16 n17 n18 n19 n13 n14 n15 n21 n22 n30 n26 n27 n28 n29 n23 n24 n25 GND IN9 IN10 IN11 IN12 4 x 0 10V GND IN13 IN1...

Page 19: ...N17 COM 13 16 IN13 IN14 IN15 IN16 IN18 n01 n02 n03 n04 n05 n06 n07 n08 n09 n10 n11 n12 n13 n14 n15 n16 n17 n18 n19 n20 n21 n22 n23 n24 n25 n26 n27 n28 n29 n30 GND IN9 IN10 IN11 IN12 4 x 0 20mA GND IN1...

Page 20: ...Manual For CONTROLLER DATA RECORDER MultiCon CMC 99 141 Fig 4 12 Isolated current input modules 20 IS6 6 isolated current input IN 1 n01 n02 n03 n04 n05 n06 n07 n08 n09 n10 n11 n12 IN 2 IN 3 IN 4 IN 5...

Page 21: ...s 2 current inputse n03 n04 n05 n01 n02 GND IN1 IN2 IN3 IN4 2 x 0 20mA 2 x 0 20mA flowmeters FT2 2 pulse inputs 2 current inputs n07 n08 n09 n04 n05 n01 n02 n03 n04 n05 n01 n02 n03 n06 GND IN3 IN4 2 x...

Page 22: ...1 n02 n03 n14 n15 n16 n12 n13 n09 n10 n11 IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN_T TC4 4 thermocouple inputs n06 n07 n08 n04 n05 n01 n02 n03 IN1 IN2 IN3 IN4 IN_T TC12 12 thermocouple inputs n06 n07 n08 n0...

Page 23: ...ig 4 15 RTD input modules 23 RT4 4 RTD inputs n08 n09 n10 n11 n12 n04 n05 n06 n07 n01 n02 n03 n16 n13 n14 n15 IN1 IN2 IN3 IN4 RT6 6 RTD inputs IN1 IN2 IN3 IN4 IN5 n08 n09 n10 n11 n12 n04 n05 n06 n07 n...

Page 24: ...n11 n12 n04 n05 n06 n07 n01 n02 n03 n13 n14 n15 V mA TC mV RTD IN1 TC mV RTD IN2 TC mV RTD IN3 V mA V mA IN_T UN5 5 universal inputs n08 n09 n10 n11 n12 n04 n05 n06 n07 n01 n02 n03 n13 n14 n15 V mA TC...

Page 25: ...OM 5 8 IN18 IN19 IN20 IN21 IN17 D8 8 Digital inputs IN3 IN1 IN2 IN4 COM 1 4 IN5 IN6 IN7 IN8 COM 5 8 n08 n09 n10 n04 n05 n06 n07 n01 n02 n03 IN9 IN10 IN11 D24 24 Digital inputs n08 n09 n10 n11 n12 n04...

Page 26: ...ter 4 Prg2 Inp21 Inp22 Res2 COM2 Prg3 Inp31 Inp32 Res3 COM3 Prg4 Inp41 Inp42 Res4 COM4 HM4 4 hourmeters n06 n07 n08 n04 n05 n01 n02 n03 n10 n11 n12 n09 COM 1 START STOP 1 PRG 1 COM 2 START STOP 2 PRG...

Page 27: ...OUT8 GND OUT9 10 24V DC OUT10 OUT11 OUT12 OUT13 OUT14 OUT15 OUT16 GND n01 n02 n03 n04 n05 n06 n07 n08 n09 n10 n11 n12 n13 n14 n15 n16 n17 n18 n19 n20 S24 24 SSR outputs n08 n09 n10 n11 n12 n04 n05 n0...

Page 28: ...T1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT9 OUT10 OUT7 OUT8 OUT11 OUT12 R65 6 relay outputs 5A 250V n01 n02 n03 n04 n05 n06 n07 n08 n09 n10 n11 n12 n13 n14 n15 n16 n17 n18 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 R81 8 rel...

Page 29: ...09 n10 n11 n12 OUT 2 PASSIVE OUT 1 PASSIVE IO4 4 current output n05 n06 n03 n04 n01 n02 n07 n08 OUT 4 PASSIVE OUT 3 PASSIVE OUT 2 PASSIVE OUT 1 PASSIVE IO2 2 current output OUT 2 PASSIVE OUT 1 PASSIVE...

Page 30: ...n CMC 99 141 device supports the following converters USB RS 485 converter SRS USB 4 Z45 RS 232 RS 485 converter SRS 2 4 Z45 30 RS232 RS485 or USB RS485 interface 8 6 7 RS 485 GND A B RJ 45 ETH USB ho...

Page 31: ...MultiCon CMC 99 141 5 1 UNDERSTANDING CONTROLLER DATA RECORDER MultiCon CMC 99 141 The MultiCon CMC 99 141 device was developed as a universal multichannel controller To maintain this concept its fir...

Page 32: ...to other Logical Channels data source for visualisation and logging Depending on type the device can be equipped with different number of Logical channels and other functions Their amount is shown in...

Page 33: ...tes of virtual input channels and timers mathematical combination of other Logical Channels 33 Logical channel 1 2 3 4 5 LC External output output address port Remote Modbus output 1 1 1 100 255 1 1 2...

Page 34: ...ed for other processes It is common that channels belonging to the same Group are related to one another in some way for example representing parameters of single object or representing similar parame...

Page 35: ...Ethernet RJ 45 connector see Fig 4 22 Three slots designed for built in hardware inputs and outputs are installed on the right side of the case see Fig 4 8 terminals marked slot A slot B and slot C T...

Page 36: ...astic or another soft material with round ends for example the pionter delivered with the device or a finger The display of the MultiCon CMC 99 141 should also be protected against aggressive substanc...

Page 37: ...date actual time and date display on the right upper corner on the screen can be set in General settings see Chapter 7 7 GENERAL SETTINGS logging data indicator located in the Information bar the log...

Page 38: ...ged data is moved to memory Note at this time you must not turn off the device because it may cause a loss of recently logging data In order to turn off the device especially when the data logging is...

Page 39: ...er has to enter the password before entering the configuration Fig 6 4 Methods for direct entry to Logical channel configuration 1 and Group configuration 2 6 3 3 Data panels The great deal of the scr...

Page 40: ...it denoted by 3 channel s name denoted by 4 on some modes there is also a visible percentage indicator of the value in relation to it s full scale denoted by 5 Every Group of Logical Channels can be p...

Page 41: ...mples of Horizontal for 3 channels and Vertical Bars for 5 channels Fig 6 8 Examples of Horizontal for 3 channels and Vertical Charts for 5 channels Fig 6 9 Examples of Phasor Charts presentation mode...

Page 42: ...een for example groups starting from group 8 will display on the screen starting from the left side of the page groups 8 9 10 1 2 See Chapter 7 14 GROUPS for more information about Groups 6 3 4 Import...

Page 43: ...bols see Fig 7 3 diacritical letters Fig 7 4 font and background colors see Fig 7 5 values editor which is divided into tabs decimal form see Fig 7 6 hexadecimal form see Fig 7 7 binary form see Fig 7...

Page 44: ...ckground color selection Fig 7 6 Value editor decimal form Fig 7 7 Value editor hexadecimal form Fig 7 8 Value editor binary form Fig 7 9 Single choice type editor Fig 7 10 Multiple choice type editor...

Page 45: ...element from the list Navigation keys in choice type dialogues Move arrows Allow to move cursor along the edited text Caps lock switches between lower and upper case letters Backspace When editing val...

Page 46: ...s are described in further chapters Chapter 7 5 Chapter 7 3 Chapter 7 4 Fig 7 13 Main menu window The Safe shutdown button allow for a safe power down of the device After pressing the button and accep...

Page 47: ...called Logging files Configuration files Permission files and Printer files The Logging files button is always visible and it contains all possible parameters but their functionality is blocked until...

Page 48: ...window with a list of damaged files is dispayed the damaged logging files are those that contain errors caused by inappropriate shutdown the device during data logging There is no guarantee that this...

Page 49: ...ce is equipped with one of the communication modules In step 1 press the button Press to select next to the Group 01 label In step 2 select 2 files by pressing the selected files and then choose the b...

Page 50: ...tings built in external inputs settings built in external output settings Modbus protocol settings profile timer settings control settings network settings group settings Load save Modbus templates al...

Page 51: ...emplate file with extension mcfg for Modbus slave template file with extension scfg Please note that the file name is defined by the user If the user wants to Save configuration Modbus template press...

Page 52: ...t contain those settings Fig 7 23 Enter password dialogue Printer files Fourth button in the Files management menu is Printer files It is always visible but functionality is active only when to the d...

Page 53: ...hardware configuration a list of installed modules number of slot module type network settings active licences Enter licence key button see Fig 7 27 allows the user to enter a licence key purchased fr...

Page 54: ...Xming 6 9 0 31 Xming 6 9 0 31 setup exe download 2 Install Xming on your PC using default settings During installation enable create a desktop icon for Xming option and disable Launch Xming option 3 A...

Page 55: ...pensate work temperature effect To do this press Service options button and pass the password which is RTC CALIB and then enter current time and date After at least two weeks password should be entere...

Page 56: ...ner of the screen Due to the fact that the configuration process takes place in real time all changes must be confirmed before saving them In the confirmation window you can Save or Revert changes see...

Page 57: ...CMC 99 141 Chapter 7 7 Chapter 7 8 Chapter 7 9 Chapter 7 10 Chapter 7 11 Chapter 7 12 Chapter 7 13 Chapter 7 14 Chapter 7 15 Chapter 7 16 Chapter 7 17 Chapter 7 18 Chapter 7 19 Fig 7 29 Main menu sele...

Page 58: ...User Manual For CONTROLLER DATA RECORDER MultiCon CMC 99 141 Fig 7 31 Warning message about unsaved configuration Fig 7 32 Example of unsaved configuration screen view 58...

Page 59: ...Add a new view Delete this view Move to pos External outputs Mode Alarm state Level Lower level Upper level Hysteresis Source ON delay OFF delay Min ON time Min OFF time Timing Levels Binary output A...

Page 60: ...High limit Mode Source analog input Wire compensation Totalizer Base unit Offset Zero time Source digital input Filter Reset now Counting mode Reset mode Prog inp mode Low limit High limit Unit Base u...

Page 61: ...Logging options Channels Mode Description Alternative mode Besa period Base unit Alternative unit Alternative source Alternative period Rotation direction Offset Labels Theme Theme Theme Theme Theme T...

Page 62: ...blocks Avail output blocks Block type Register size Last register First register Mode Baud rate Request retials SLAVE devices Request timeout Format SLAVE settings Interval Address 5 Edit buttons Gene...

Page 63: ...ster addresses for Logical channel and External output menu Two formats are available hexadecimal the registers are displayed in hexadecimal format To indicate that data has a hexadecimal format the l...

Page 64: ...isplay to change every time period The parameters of this block include Change mode this parameter has the following options disabled no changes in the display For this mode the remaining parameters i...

Page 65: ...e shutdown procedure won t start To start shutdown procedure value in this channel must change to value equal or lower than 0 and then to value greater than 0 Setup list parameter After pressing the S...

Page 66: ...view 4 To add or delete further views use the Add a new view button or Delete this view button respectively 5 When the user wants to add a view between the existing views e g between views 2 and 3 us...

Page 67: ...password before entering the configuration 7 8 1 Logical Channels General settings Arrows placed in the upper right corner of the screen allow you to switch between a succession of logical channels Th...

Page 68: ...hapter 7 8 8 Profile timer cycle counter see Chapter 7 8 9 Data from other channel see Chapter 7 8 10 Latch parameter block allows user to set the latch function which will hold the last value of a ch...

Page 69: ...tains following options Input value value of point 1 before scaling Output value value of point 1 after scaling Point 2 block contains following options Input value value of point 2 before scaling Out...

Page 70: ...ling configuration c offset after choosing this option parameter appears Configure scaling function which allows to add a constant value to input value It is given by formula In this function there ar...

Page 71: ...articular point from the list For 2 points the user characteristic works like a linear process see subsection b For more than 2 defined points the user characteristic is a composite of the line charac...

Page 72: ...u want to create an output Unit which replaces the input unit or if no unit is defined on the input press the button next to Output Unit label 4 Press the Edit points button point 4 in Fig 7 35 and go...

Page 73: ...formula where n number of sample where n 1 2 3 Yn output value for n th sample Yn 1 output value for n 1 sample Xn input value for n th sample w time constant in seconds this filter coefficient is def...

Page 74: ...configuration parameters of this filter Mode allows to choose filter work mode peaks function detects highest values in logical channel valleys function detects lowest values in logical channel Value...

Page 75: ...the pattern as default Precision this parameter occurs when Format parameter is set as numeric or time which specifies the precision to be displayed on the output value see Fig 7 39 Off state text thi...

Page 76: ...middle part of the number on the screen part 3 of 3 display the lowest part of the number on the screen For time Format in logical channel only 6 digits three special signs colons dot but not more tha...

Page 77: ...u 2 different kinds of Displaying parameters To calculate percentage which will be displayed on the indicator the device is using following equation where R result V value in logical channel Lo Graph...

Page 78: ...ve and the highlight variant with lower number will appear generated will the one with lower number even if the Trig hold time of the first one will not expire Trigger using this parameter user can ch...

Page 79: ...on Example 1 Task User s task is to set blinking highlight on alarm channel which will be active when measured current value is too high or too low Solution After connecting all measuring devices and...

Page 80: ...binary In Off state text parameter write No alarm In On state text parameter write ALARM In Graph low parameter write 0 In Graph high parameter write 22 Now we go to Channel highlight submenu Highlig...

Page 81: ...parameter set as enabled In Unit parameter write C Precision parameter set as 0 0 In Graph low parameter write 50 In Graph high parameter write 85 All other parameters should be set as default Logical...

Page 82: ...nel 6 Calculating the time of the third alarm In Name parameter write Calc Third level Mode parameter set as Math function Click on the Function button Function parameter set as X Y Source X parameter...

Page 83: ...o Color parameter and set font color at the top of screen and background color at the bottom of the screen Highlight color parameter set as 3 Mode parameter set as blinking In Blink period parameter w...

Page 84: ...od to change the source configuration is to use the Built in inputs menu see Chapter 7 9 BUILT IN INPUTS Latch parameter block allows user to set the latch function which will hold the last value of a...

Page 85: ...8 the list of currently available modules is on the website Description of input modules parameters is shown in Chapter 7 9 2 Built in inputs Input modules The following steps change the Source confi...

Page 86: ...hapter 7 9 3 Built in inputs Binary input Inp X2 Digital 24V c built in Demo input numbered Inp X3 Demo Inp X4 Demo Inp X5 Demo The device has 3 built in simulation Demo inputs which can be defined by...

Page 87: ...utput monitor in this parameter user selects the source of data for logical channel Source in this parameter user selects the source of data from the available built in outputs list for the logical ch...

Page 88: ...e Hardware output monitor mode can be in the same order as in the list in device see Fig 7 45 installed hardware output modules in the respective slots A B or C see Fig 4 8 a list of modules currently...

Page 89: ...ode are see Fig 7 46 Name it gives the name to the logical channel Unit to create a unit use the Scaling parameter in Processing parameter block more information see Chapter 7 8 1 Logical Channels Gen...

Page 90: ...er to set the latch function which will hold the last value of a channel discussed in Chapter 7 8 1 Logical Channels General settings Processing parameter block is used for scaling and filtering data...

Page 91: ...formation about the Modbus protocol implemented in the MultiCon see Chapter 7 15 MODBUS 91 i Port MB1 SLAVE Device Address 1 Device input Register 0 SLAVE Device Reg 0 Reg N SLAVE Device Reg 0 Reg N S...

Page 92: ...tton in the panel data see Fig 7 49 this parameter has two options disabled the button is disabled on the display in this case the data source of logical channel will be the value set in the Set point...

Page 93: ...n the screen discussed in Chapter 7 8 1 Logical Channels General settings Fig 7 49 Data panels for Logical channel in Set point value mode Fig 7 50 Configuration of the value for Logical channel in Se...

Page 94: ...and On state text channel value 1 in the Displaying parameter block b for enabled latch function For format numeric and time after pressing the button an edit window appears allowing entry of value s...

Page 95: ...or it can be the data source for an output to control and set any object The parameters of Logical channel in Math function mode are Name it gives the name to the logical channel Unit to create a unit...

Page 96: ...ions Depends of Type of source X parameter This parameter allows user to select logical channel from list Type of source Y channel or enter set point value Type of source Y value X error handling avai...

Page 97: ...rs J input mode available for Function flip flop the user can set following options always 0 flip flop J input is always in logical state 0 always 1 flip flop J input is always in logical state 1 from...

Page 98: ...ertain math functions Available types are channel meaning that the Y source will be a logical channel selected from a list in Source Y parameter value means that the Y source will be a constant value...

Page 99: ...User Manual For CONTROLLER DATA RECORDER MultiCon CMC 99 141 Fig 7 53 Sample configuration of logical channel in Math function mode 99 1 2 3 4 5 6 7...

Page 100: ...Y 0 Logical XOR 1 XOR 2 result 1 when the value of the one channel is greater than 0 and the value of second channel is 0 When both channels have values 0 or when both channels have values 0 then the...

Page 101: ...1 otherwise it will be 0 ALL X i Y The result 1 if all values of selected channels are smaller than the value of the channel or constant value Y ALL 1 2 3 4 5 the result is 1 if all values of channel...

Page 102: ...min 1 reset by 4 minimal value of channel 1 reset by channel 4 max X reset by Y Maximal value of selected channel X if value of channel Y 0 or current value of X reset if value of Y 0 max 1 reset by...

Page 103: ...k 1 0e 8 k ERROR Function arctan X If absolute value of X in radians is lower than one hundred millionth then the function result will be 0 in other way abs X rad 1e 8 arctan X 0 If absolute value of...

Page 104: ...than 0 and Y is not integer then logical channel will be in Err state in other way X 0 Y C ERROR Function logy X If X or Y is lower than 1 40129846 10 45 then logical channel will be in Err state in...

Page 105: ...or logical channel Unit this parameter allows the user to define the unit Controller number this parameter allows the user to select a controller from the list 1 8 User must configure the selected con...

Page 106: ...for scaling and filtering data discussed in Chapter 7 8 1 Logical Channels General settings Displaying parameter block for these parameters the user select format and range of data displayed on the sc...

Page 107: ...more information see Chapter 7 8 1 Logical Channels General settings Mode Profile timer in this parameter user selects source of data for logical channel Source this parameter allows the user to selec...

Page 108: ...annels General settings User must configure the Profile timer parameters in the Profiles timers menu before using this Profile timer to control real object To read more about Profiles timers profiles...

Page 109: ...rofiles timers are implemented in the device the selected option will be the data source for this logical channel Configure source this button allows the user to configure the Profile timer selected i...

Page 110: ...gives the name to the logical channel Unit the unit downloaded from the source logical channel to change the unit use the Scaling parameter in the Processing parameter block for more information see C...

Page 111: ...nd then to the device in accordance with Fig 7 57 Fig 7 57 Schematic diagram for the UI4 module In the next step you need to define three logical channels for current voltage and power To do this a Fo...

Page 112: ...nnel such as 21 in Name parameter write Voltage Mode parameter set as Hardware input Source parameter set as Inp A5 Voltage see the connection in Fig 7 57 press the Source configuration button to set...

Page 113: ...User Manual For CONTROLLER DATA RECORDER MultiCon CMC 99 141 Fig 7 58 Current and voltage source configuration example 113 5 3 6 7 8 9 4 1 2...

Page 114: ...parameter set as channel Source Y parameter set as logical channel 21 which is defined as reading of the heater voltage Scale parameter set as linear press Configure scaling button in Output unit para...

Page 115: ...els to view them in one window on the screen To do this enter the Group menu and turn it on if its off in Name parameter write Heater for Channels block parameters Slot 1 parameter set as logical chan...

Page 116: ...last step is to define the Initial view see Fig 7 61 displayed on the LCD screen when the device starts Initial View has to display a defined group of logical channels power voltage and current in ne...

Page 117: ...set to disabled as in this example we want to all the time displayed only Group 1 in the same needle mode after setting all parameters exit the General settings menu Fig 7 61 An example of Initial vi...

Page 118: ...nnels respectively for four temperatures in the hall of the symbols A1 A2 A3 A4 and an temperature alarm condition To do this a For the temperature reading of sensor 1 with the symbol A1 touch screen...

Page 119: ...Using the arrows in the top navigation bar select any Logical channel except for 1 2 and 3 for example 4 in Name parameter write Temperature A4 Mode parameter set as hardware input Source parameter se...

Page 120: ...mode To do this enter in the General settings menu Basic block parameters left unchanged unless indicated date and time were to set incorrectly and should be improved for LCD screen block parameters B...

Page 121: ...ld configure the device and then connect the sensors as shown in Fig 7 65 Fig 7 65 Schematic diagram for the RT4 module In first step you need to configure Logical channels To read the temperature fro...

Page 122: ...ameter set as Logical channel 32 called the Basement Slot 5 parameter set as Logical channel 33 called the Corridor Slot 6 parameter set as empty for Logging options block parameters this block of par...

Page 123: ...user should configure the device and then connect them as it is shown in Fig 7 67 After setting the configuration of the physical inputs can configure the input channel to read the output value Fig 7...

Page 124: ...l channels to view them in one window on the screen To do this enter the Group menu to enable the Group 1 if it is off in Name parameter write Monitor output for Channels block parameters Slot 1 param...

Page 125: ...avigation bar select any logical channel such as 1 in Name parameter write Temperature 1 Mode parameter set as Modbus Port parameter set as MB1 MASTER SLAVE devices parameter set as Addr 1 Temp conver...

Page 126: ...xt step you need to define Group the set up logical channels to view them in one window on the screen To do this enter the Group menu to enable the Group 1 if it is off in Name parameter write Tempera...

Page 127: ...low the same way as in 7 8 11 2 Application of Logical channel in the Hardware input mode for TC4 modules For Logical channel in Math function mode calculated an average value touch screen and press t...

Page 128: ...ed the Temperature 4 Slot 6 parameter set as logical channel 5 called the Temperature 5 all other parameters in this Group should be on default settings using the arrows in the top navigation bar sele...

Page 129: ...The result of this function is placed in Tab 7 4 Y value Value of logical channel 3 Y 0 Value of logical channel 1 0 Y 1 Value of logical channel 5 1 Y 2 Value of logical channel 8 Y 2 Value of logica...

Page 130: ...al channel in Math function mode using the arrows in the top navigation bar select logical channel 1 in Name parameter write Function Mode parameter set as Math function enter Function submenu to sele...

Page 131: ...ng to 7 13 2 1 Application of the Controllers Next is to configure logical channels as follows For demanding object temperature value touch screen and press the Menu button press the Device configurat...

Page 132: ...00 C For channel settings in Controller mode touch screen and press the Menu button press the Device configuration button enter Logical channels menu using the arrows in the top navigation bar select...

Page 133: ...hown in Fig 8 41 see also Appendices 8 2 UI4 UI8 UI12 U16 U24 I16 I24 VOLTAGE and CURRENT MEASUREMENT MODULES Fig 7 73 Example of Profile waveform For logical channel in Profile timer mode touch scree...

Page 134: ...value parameter write 4 press green button on the bottom left side of the screen Section num parameter should be set as 4 in Duration parameter write 1 Unit parameter set as second Shape parameter se...

Page 135: ...input mode touch screen and press the Menu button press the Device configuration button enter Logical channels menu using the arrows in the top navigation bar select any logical channel in this examp...

Page 136: ...et as 0 00 in Graph low parameter write 0 dm3 s in Graph high parameter write 100 dm3 s To display Total flow using the arrows in the top navigation bar select logical channel 2 in Name parameter writ...

Page 137: ...uts General settings Available in the device in the basic configuration is 4 Built in inputs Digital input and 3 Demo inputs and input modules installed in the device depending on the customer s needs...

Page 138: ...Built in inputs menu The Built in inputs can be in the same order as list in the device see Fig 7 25 a installed input modules in the appropriate slots A B or C see Fig 4 8 the list of currently avai...

Page 139: ...dy has a name given by the device and user cannot change it description of the Name parameter see Fig 7 75 Unit it is related to channel source data for built in modules default unit appears automatic...

Page 140: ...e output displayed as status Lo High limit the value above which there is a high state at the output displayed as status Hi Minimum simulated value lowest generated signal level Maximum simulated valu...

Page 141: ...parameter see Fig 7 75 Unit parameter which displays measurement unit mA Mode defines measurement range Low limit defines measurement level bellow which in logical channel will be displayed Lo state...

Page 142: ...Equation allows to choose method of entering thermistor characteristic There are two possibilities equation with Beta parameter where A resistance in reference temperature B 25 100 parameter C refere...

Page 143: ...in selected channel Each flow channel is equipped in IN n input and common ground GND All analogue channels are galvanically separated from the device The user can thanks to Scaling parameter in Logic...

Page 144: ...sensor and calculating total flow in selected channel Each pulse channel is equipped in counting inputs Inp n 1 Inp n 2 and common ground COM n All pulse channels are galvanically separated from the...

Page 145: ...when value in this channel will be greater than 0 Strobe mode turns on and off total flow calculating from logical channel Strobe source allows to choose logical channel from list which will hold tot...

Page 146: ...measured sensor value automatic allows to compensate the difference between real temperature and that measured by the sensor Actual temperature parameter in which user enters actual temperature near t...

Page 147: ...ferent but it can be changed in certain limits High limit defines measurement level above which in logical channel will be displayed Hi state for each sensor this limitation is different but it can be...

Page 148: ...Lo state High limit defines measurement level above which in logical channel will be displayed Hi state Offset parameter which allows to add or subtract constant value to temperature measured by conn...

Page 149: ...arameters disable no additional resets from log channel an additional reset is logical channel selected from list in Reset source parameter it is activated by high state external an additional reset i...

Page 150: ...nnot change it for description of Name parameter see Fig 7 75 Unit parameter which displays measurement unit sec Mode read only parameter which displays measured physical quantity Time Low Limit value...

Page 151: ...reset or inhibits the counter when rising edge occurs and Prog inp mode parameter is set as inhibit but in this case the counter will start counting again when on Start Stop input new trigger occurs...

Page 152: ...is 17 Built in outputs Sound signal and 16 Virtual relays and output modules installed in the device depending on customer s needs Configured output can be used to control any process or can be used...

Page 153: ...output modules slot tag and type of module is in Hardware configuration parameters block in Device information menu see Fig 7 25 in Chapter 7 4 Fig 7 80 Main settings of disabled left and enabled righ...

Page 154: ...he selected logical channel will be a data source for this built in output see Fig 7 79 Alarm state this parameter allows to choose type of output reaction in case of alarm state appearance The Alarm...

Page 155: ...vel if Source value is higher than Level value high state on output appears bellow level if Source value is lower than Level value high state on output appears Lower level and Upper level these parame...

Page 156: ...he output switch from low to high state see Fig 7 84 OFF delay this parameter allows the user to set the time that must pass from the time of exceeds Level value until the output switch from high to l...

Page 157: ...le of relay output operation for sample timing settings Min ON time 5 sec Min OFF time 4 sec 157 Time s Zone A Zone B Output value Zone A Zone B Level Time s t 5s t 4s Input value 1 2 3 4 5 6 7 8 9 10...

Page 158: ...t the range of the input signal which will change the duty cycle of the output signal is discussed below in this Chapter Timing parameter block these parameters allow the user to set the timing parame...

Page 159: ...er level 14 input signal lower than 4 has tn 0 higher than 14 has tn 1 Timing parameter block The parameters of this block include Period the duration of one cycle of output pulse the minimum value is...

Page 160: ...ist where the selected logical channel will be a data source for this built in output data from this source are calculated according to parameters gathered in Input levels and Output levels blocks Inp...

Page 161: ...on 3 22mA Alarm state is when source logical channel returns Err or the state of exceeding range the low Lo state and high Hi state Lower level and Upper level parameter describe the transfer equation...

Page 162: ...output modules To control temperature in object shown on Fig 7 92 it is necessary to configure one Logical channel and Relay output For reading PT100 sensor temperature touch screen and press the Men...

Page 163: ...the Built in outputs menu using the arrows in the top navigation bar select a relay output which is connected to heater For this example it is the output named Out C1 Relay see Fig 7 92 Mode paramete...

Page 164: ...elect a current output on which we want to generate current in demanded range e g Out C1 Current Source parameter set as Logical channel 1 which returns pressure value in range 100 500 bars for Input...

Page 165: ...l outputs as will be defined in the Modbus menu see Chapter 7 15 3 Modbus MASTER mode In case when the external outputs are not defined or inactive than in External outputs menu is an empty list Exter...

Page 166: ...ports configuration and view of the Modbus port connectors is located in Chapter 7 15 MODBUS Device this parameter is read only in External outputs menu it shows address and name of the SLAVE device...

Page 167: ...VE device as defined in a specific address has its output list individually numbered Mode this parameter allows the user to select the method of the external output operation depending on source signa...

Page 168: ...or the mode above level above the level we get high state at the output below level below the level we get high state at the output Lower level and Upper level these parameters define the range at whi...

Page 169: ...s list where the selected logical channel will be data source for the external output Data from this source are calculated according to parameters in Input levels block and Output levels block Input l...

Page 170: ...Modbus MASTER Device channels parameter block for undefined Source parameter e g a Logical channel in the Mode disabled or for undefined Input and Output levels parameter block every parameter has val...

Page 171: ...485 to the output To do this touch screen and press the Menu button press the Device configuration button enter the Logical channels menu using the arrows in the top navigation bar select any Logical...

Page 172: ...vel parameter write 0 in Upper level parameter write 65535 for Output levels block parameters in Lower level parameter write 0 in Upper level parameter write 65535 in Alarm level parameter write 0 usi...

Page 173: ...e window on the device screen To do this touch screen and press the Menu button press the Device configuration button enter the Groups menu in Name parameter write Flowmeter for Channels block paramet...

Page 174: ...y Logical channel switched to Profile timer mode Fig 7 80 see also Chapter 7 8 8 Logical Channels Profile timer mode Fig 7 98 Block diagram of the device configuration for generating Profiles timers 1...

Page 175: ...rom source signal After the rising edge the Profile will be generated in whole once regardless of further changes to the signal source For more details see Chapter 7 12 2 Profiles timers Triggering mo...

Page 176: ...s channel If Profile timer is paused and new trigger will be detected the Profile timer will react on this trigger like it would not be paused Pause source this parameter is not visible when Pause mod...

Page 177: ...right corner of the screen allow switching between sections Middle button allows direct selection of a specific section The Section list parameters are Duration defines duration of the section it depe...

Page 178: ...e Profile timer there are five modes of triggering disabled level gate this means that configured by user Profile is generated when source signal will have a value 0 otherwise if source value 0 define...

Page 179: ...ount parameter from logical channel allows to run the profile number of times equals the value in the selected logical channel determined by the Looping source parameter infinite allows to infinite re...

Page 180: ...to the Profile timer Triggering mode on time allows to trigger the Profile at demanded time defined in Triggering times parameter Triggering times submenu with the parameters which defines times of Pr...

Page 181: ...ogical channel It allows to choose a logical channel from the list which value will be compared with the number of already made cycles of Profile Return to position this parameter is invisible if Loop...

Page 182: ...2 which is connected to current input of UI4 module Profile consists of four segments 1 ramp from 0 to 10 during 5 seconds 2 const value 8 during 2 seconds 3 ramp from 8 to 4 during 3 seconds 4 const...

Page 183: ...om left side of the screen to configure Section num 1 in Duration parameter write 5 sec Unit parameter set as second Shape parameter set as ramp in Final value parameter write 10 press the green plus...

Page 184: ...rameter write 0 in Graph high parameter write 10 The way of configuring logical channel Triggering source in Hardware input mode for current input is shown in 7 8 11 1 Application of Logical channel i...

Page 185: ...side of the screen enter the Seconds menu and press the icon on the bottom left side of the screen enter the Section list submenu press the green plus at the bottom left side of the screen to configu...

Page 186: ...ts to minimize the error by adjusting the process control outputs In the device there is 8 independent settings of PID type controllers available 7 13 1 Controllers General settings In the system ther...

Page 187: ...fficient this parameter is available for PD and PID mode and allows to set the derivative coefficient Differentiated signal this parameter is available for PD and PID mode and allows the selection of...

Page 188: ...from the object controlled MultiCon uses data collected from these channels and the corresponding Controller controls the object Fig 7 109 Block diagram of the control loop of the object by MultiCon F...

Page 189: ...ice Example of this connections are shown on Fig 7 111 Fig 7 111 The connection scheme for RT4 module and Modbus MB1 port In the first step we define Controller settings touch screen and press Menu bu...

Page 190: ...k is to configure the controller which will control the heater using SSR output in order to obtain a constant object temperature A logical channels with set point value and temperature from thermocoup...

Page 191: ...or temperature measurement module TC4 installed in slot A and SSR output driver module S8 installed in slot C to control a heater keeping set temperature of the object Lets assume that temperature set...

Page 192: ...on 0 Graph Lo 0 Graph Hi 300 all other parameters should be on default settings for Logical channel 3 Name PID controller Mode Controller Controller num 1 PID Controller 1 Set point channel Log ch 2 D...

Page 193: ...oup is active Name it gives the name to the Group Charts sets the chart type whet group is displayed in this mode horizontal time axis is in horizontal position vertical time axis is in vertical posit...

Page 194: ...s sets the bars type when group is displayed in this mode horizontal horizontal direction of bars position vertical vertical direction of bars position Fig 7 115 Examples of Horizontal and Vertical Ba...

Page 195: ...s if the device was on or off see Fig 7 117 Samples which were not measured will be displayed as 0 when time when the device was off does not fits between moving vertical markers on the screen repeate...

Page 196: ...gical channels which will be displayed in the specific location on the screen Style defines color which will be used to draw logical channel selected in this Slot User can specify font color in channe...

Page 197: ...ONTROLLER DATA RECORDER MultiCon CMC 99 141 Fig 7 119 Sample of Group parameters settings all Slot set to Logical channel Fig 7 120 Sample of Group parameters settings Slots set to Logical channel and...

Page 198: ...UPDATE REMOTE DISPLAY EXPORT MANUAL AND RENEW CONFIGURATION To log the data from the Logical Channel should be Logical channel attached to Group using the Channels parameter block see Chapter 7 14 1 G...

Page 199: ...duration form 0 1 to 24 hour Alternative mode this mode allows the user to log data in special situation where a deeper analysis is required for example in critical state of object this parameter has...

Page 200: ...gical channel in the Hardware input mode for RT4 modules We need to define Group with logical channel in order to display it on the device screen To do that enter Groups menu and turn on Group 1 if it...

Page 201: ...t 1 parameter set as Logical channel 1 named Pressure Slot 2 parameter set as Logical channel 2 named Temperature Slot 3 parameter set as Logical channel 3 named Humidity Slot 4 6 set as disabled all...

Page 202: ...between MultiCon and other device using TCP IP protocol port number 502 must be unlocked in software and hardware firewall Fig 7 125 Serial communication ports available in the device 202 SERVICE Pow...

Page 203: ...us port is inactive SLAVE this device is SLAVE device see Chapter 7 15 2Modbus SLAVE mode MASTER this device is MASTER device and manages the Slave devices see Chapter 7 15 3 Modbus MASTER mode 7 15 2...

Page 204: ...tton allows the loading of a template with predefined blocks of input registers for more information see Chapter 7 15 2 1 Modbus SLAVE Modbus Templates for SLAVE mode Save device template this button...

Page 205: ...submenu where the user can configure registers of available logical channels In this submenu the user decide which registers are read only or read and write Avail output blocks submenu where the user...

Page 206: ...ions 32 bits signed integer value the most significant bit is the sign bit 32 bits unsigned integer value without information about the sign 32 bits float floating point IEEE 754 format 32 bits BCD un...

Page 207: ...type parameter is set as read HOLDING reg in this block registers are read type When this block is set as write HOLDING reg in this block register are read and write type 7 15 2 3 Modbus SLAVE The Mod...

Page 208: ...or logical channel 1 low word 402h No 0 0FFFFh Status for logical channel 1 0h data valid 1h data not ready 20h software error 40h bottom border of the software measurement range is exceeded 80h top b...

Page 209: ...f the device in the system FUNC Function number REG H L Higher and lower part of registry number to which the command refers to COUNT H L Higher and lower part of registry counter number to which the...

Page 210: ...options are shown in the Tab 7 8 Format Number of data bits parity control Number of stop bits 8N1 8 none 1 8N2 8 none 2 8E1 8 even 1 8E2 8 even 2 8O1 8 odd 1 8O2 8 odd 2 Tab 7 8 Data format of the RS...

Page 211: ...e type is set to defined or a Template has been loaded then extended SLAVE device menu is shown This menu as following fields Device type defined Device name to create or change the name of a SLAVE de...

Page 212: ...eter block This block includes following buttons Input list submenu where the user can define logical channels with chosen write registers Output list submenu where the user can define logical channel...

Page 213: ...er settings for more info Channel status HI parameter block allows to define when a status HI should be displayed returned in a place of numerical value of Input Channel HI state defines condition for...

Page 214: ...s parameter is only for the register settings in the Input list menu for the Output list menu the registers are HOLDING type a user can select two types HOLDING holding registers of SLAVE device compa...

Page 215: ...en SLAVE devices has a limitation of max number of registers read in a single frame Block list occurs only for manual mode parameter description bellow in this chapter Avail Input blocks read only sub...

Page 216: ...ck list parameters according to Input list and Output list in Device channels parameter block of the device see above in this Chapter If user creates a block of registers to read preset in which there...

Page 217: ...which contains temperature register 2 is a status register register 3 is a decimal point register The devices has addresses 1 and 8 To set Modbus configuration for the same devices Modbus template can...

Page 218: ...129 Mode parameter set as MASTER Baud rate parameter set as 9600 bits sec it should be the same as in the SLAVE device Format parameter set as 8N1 in Request timeout parameter write 0 2 sec in Reques...

Page 219: ...LO state parameter set as if register value in the LO register parameter set Register type parameter set as HOLDING in Register number parameter write 2h Data format parameter set as 16 bits unsigned...

Page 220: ...meter output channel The Slave device address is 5 we write data to register 1 2 4 and 8 For communication in this task we use ACM module in which the port MB2 is used Solution First we need to config...

Page 221: ...5 Device type parameter set as defined in Device name parameter write Flowmeter in the Device channels parameter block press the Output list button to define the register to write if the Output list i...

Page 222: ...t register parameter write 1h in Last register parameter write 2h create next block by pressing sign Block type parameter set as write HOLDING reg Register size parameter set as 16 bit registers accor...

Page 223: ...nds before the IP address is obtained from the DHCP server if user set this option other parameters in this menu is invisible IP address this parameter is visible only if DHCP parameter is set as disa...

Page 224: ...es and correct it s time according to downloaded server time If DHCP parameter is set as disabled the parameters IP address and Subnet mask must be configured correctly depending on the local network...

Page 225: ...the text box empty After that field next to Access password label will also be empty When the user passes through login process successfully on the information bar opened padlock with the letter A if...

Page 226: ...evice until manual or automatic logout MultiLevel allows to configure settings for Administrator and up to 15 users with different access levels and independent passwords Access password password whic...

Page 227: ...User Manual For CONTROLLER DATA RECORDER MultiCon CMC 99 141 Fig 7 132 MultiLevel Access password entering window Fig 7 133 User selection window Fig 7 134 Administrator password window 227...

Page 228: ...guration file They are also copied to another devices together with main configuration file Settings of MultiLevel Access protection have to be saved in independent file They are not stored in main co...

Page 229: ...w switching between printout settings Middle button allows direct selection of a specific printout from the list Printout parameters are Name gives the name to printout settings Mode turns on and off...

Page 230: ...contains following options none footer will not be printed from file allows to select and print footer Chosen footer read only parameter When footer is selected this parameter will display footer fil...

Page 231: ...be ignored Additionally this queue can not be longer than 10 messages and when it fills up appearance of new message will delete the oldest one and the new one will be placed into the queue When the...

Page 232: ...t only current values The parameters on the Notifications menu are E mail configuration menu which contains sender account parameters Mode switches notifications on and off disabled enabled Sender nam...

Page 233: ...eter which is visible only when Attachment parameter is set as groups Allows to select from list groups which must be included in the attachment Until no group is selected in this parameter all parame...

Page 234: ...Hz USB SERVICE Service port Sensor power supply output 24V DC 5 max 200mA Digital input 0 15 24V DC with galvanic insulated low state 0 1V high state 8 24V power consumption 7 5 mA 24V insulation 1min...

Page 235: ...18 n19 n13 n14 n15 GND IN1 IN2 IN3 IN4 4 x 0 20mA GND IN5 IN6 IN7 IN8 4 x 0 20mA GND IN9 IN10 IN11 IN12 4 x 0 10V GND IN13 IN14 IN15 IN16 4 x 0 10V U16 16 voltage inputs n08 n09 n10 n11 n12 n04 n05 n0...

Page 236: ...5 IN6 IN7 IN8 4 x 0 20mA GND IN21 IN22 IN23 IN24 4 x 0 10V GND IN13 IN14 IN15 IN16 4 x 0 10V GND IN17 IN18 IN19 IN20 4 x 0 10V GND IN9 IN10 IN11 IN12 4 x 0 20mA U24 24 voltage inputs n08 n09 n10 n11 n...

Page 237: ...0 22mA 4 22mA 0 5V 1 5V 0 10V 2 10V 0 20mA 4 20mA 0 6V 0 6V 0 12V 0 12V 0 22mA 4 22mA 0 5V 1 5V 0 10V 2 10V 0 6V 0 6V 0 12V 0 12V 0 20mA 4 20mA 0 22mA 4 22mA Temperature stability 50 ppm C 50 ppm C 50...

Page 238: ...0V 2 10V 0 20mA 4 20mA 0 6V 0 6V 0 12V 0 12V 0 22mA 4 22mA 0 5V 1 5V 0 10V 2 10V 0 6V 0 6V 0 12V 0 12V 0 20mA 4 20mA 0 22mA 4 22mA Temperature limitations 50 ppm C 50 ppm C 50 ppm C Internal impedance...

Page 239: ...0 10V Power supply depending on version 1 2 8 5 6 7 3 4 SERVICE 24V DC 5 Imax 200mA digital input 0 15 24V DC RS 485 GND GND A B isolated UI4 4 current 4 voltage inputs Iin1 Iin2 n08 n09 n10 n04 n05 n...

Page 240: ...ltage 240 n08 n09 n10 n04 n05 n06 n07 n01 n02 n03 GND IN1 IN2 IN3 IN4 4 x 0 20mA GND IN5 IN6 IN7 IN8 4 x 0 10V Power supply depending on version 1 2 8 5 6 7 3 4 SERVICE 24V DC 5 Imax 200mA digital inp...

Page 241: ...n02 n03 n04 n05 n06 n07 n08 n09 n10 n11 n12 n13 n14 n15 n16 n17 n18 n19 n20 UI4D8 4 current and 4 voltage 8 digital inputs GND IN1 IN2 IN3 IN4 4 x 0 20mA GND IN5 IN6 IN7 IN8 4 x 0 10V COM 9 12 IN9 IN1...

Page 242: ...5V 0 10V 2 10V 0 20mA 4 20mA 0 100k 0 6V 0 6V 0 12V 0 12V 0 22mA 4 22mA 0 110k 0 5V 1 5V 0 10V 2 10V 0 20mA 4 20mA Lo 0 0 8V Hi 2 5 5V Lo 0 4 2V Hi 11 5 30V 0 6V 0 6V 0 12V 0 12V 0 22mA 4 22mA 0 5V 1...

Page 243: ...ltiCon CMC 99 141 Measurement ranges are limited by software upon hardware inputs ability check current list of MultiCon CMC 99 141 measurement ranges at producer s website Tab 8 4 Technical data for...

Page 244: ...current input module Most important parameters of IS6 module IS6 Number of inputs 6xI Hardware limitations current inputs 3mA 30mA Hardware resolution current inputs 1 A Precision current inputs 0 25...

Page 245: ...n strength 1 min 500V AC Weight 67 g Measurement ranges are limited by software upon hardware inputs ability check current list of MultiCon CMC 99 141 measurement ranges at producer s website Tab 8 5...

Page 246: ...tability 50 ppm C 50 ppm C 50 ppm C 50 ppm C Internal impedance current inputs type 100 type 100 type 100 type 100 Protection current inputs 50mA auto reset fuse 50mA auto reset fuse 50mA auto reset f...

Page 247: ...g 58 g 52 g 72 g Measurement ranges are limited by software upon hardware inputs ability check current list of MultiCon CMC 99 141 measurement ranges at producer s website Tab 8 6 Technical data for...

Page 248: ...y depending on version 1 2 8 5 6 7 3 4 SERVICE 24V DC 5 Imax 200mA digital input 0 15 24V DC RS 485 GND GND A B isolated FT4 4 pulse inputs 4 current inputs n15 n16 n17 n04 n05 n13 n14 n01 n02 n03 n04...

Page 249: ...ocouple inputs n06 n07 n08 n04 n05 n01 n02 n03 IN1 IN2 IN3 IN4 IN_T TC8 8 thermocouple inputs n06 n07 n08 n04 n05 n01 n02 n03 n14 n15 n16 n12 n13 n09 n10 n11 IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN_T TC12...

Page 250: ...V 0 5V 0 5V Covered MultiCon CMC 99 141 measurement ranges thermocouple voltage K S J T N R E L GOST B C 10 25mV 25mV 10 100mV 100mV Temperature stability 50 ppm C 50 ppm C 50 ppm C Input impedance 6M...

Page 251: ...0 1768 5 5 0 31 E 120 4 200 1000 4 7 0 40 100 1000 2 7 0 25 L 120 4 200 800 4 4 0 44 100 800 2 5 0 28 B 30 1 250 1820 15 0 96 480 1820 6 0 45 C 120 4 50 2290 13 0 51 50 1900 9 2 0 5 with consideratio...

Page 252: ...141 measurement ranges RTD resistance Pt100 Pt 100 Pt 50 Pt500 Pt 500 Pt1000 Cu50 Cu 50 Cu100 Cu 100 0 300 0 3k Pt100 Pt 100 Pt 50 Pt500 Pt 500 Pt1000 Cu50 Cu 50 Cu100 Cu 100 0 300 0 3k 252 RT4 4 RTD...

Page 253: ...e Check current list of MultiCon CMC 99 141 measurement ranges at producer s website Tab 8 10 Technical data for the RT4 and RT6 modules type range temperature range resolution accuracy accuracy C C P...

Page 254: ...Pt 50 GOST 6651 94 W100 1 3916 Pt 100 GOST 6651 94 W100 1 3916 Pt 500 GOST 6651 94 W100 1 3916 Cu50 GOST 6651 94 W100 1 3916 Cu100 GOST 6651 94 W100 1 3916 Cu 50 PN 83M 53852 W100 1 4280 Cu 100 PN 83...

Page 255: ...05 n06 n07 n01 n02 n03 n13 n14 n15 V mA TC mV RTD IN1 TC mV RTD IN2 TC mV RTD IN3 V mA V mA n16 n17 n18 n19 n20 TC mV RTD IN4 V mA n21 n22 n23 n24 n25 TC mV RTD IN5 V mA IN_T UN3 3 universal inputs n0...

Page 256: ...or range 1 12 V for range 15 30 mV for range 15 120 mV for range 50 650 mV thermocouple inputs range 15mV 30mV range 15mV 120mV RTD inputs range 0 325 range 0 3250 1 A 1 mV 2 V 4 V 40 V 2 V 4 V 0 01 0...

Page 257: ...aintaining correct polarization 6M 4k Precision current inputs voltage inputs thermocouple inputs RTD inputs 0 1 25 C for all ranges 0 1 25 C for ranges 0 5V 1 5V 0 10V 10 100mV 0 600mV 0 15 25 C for...

Page 258: ...68 5 5 0 31 E 10 120 4 200 1000 4 7 0 40 100 1000 2 7 0 25 L 10 120 4 200 800 4 4 0 44 100 800 2 5 0 28 B 10 30 2 250 1820 15 0 96 480 1820 6 0 45 C 10 120 4 50 2290 13 0 51 50 1900 9 2 0 5 with consi...

Page 259: ...Cu 100 0 325 200 200 0 01 0 8 0 2 Ni100 0 325 60 180 0 01 0 7 0 3 Ni500 0 3250 60 180 0 1 1 4 0 58 Ni1000 0 3250 60 180 0 1 0 7 0 3 Tab 8 16 RTD measurement accuracy for the UN3 and UN5 modules type...

Page 260: ...A RECORDER MultiCon CMC 99 141 Fig 8 16 Internal structure of the optoisolated Universal input module 260 Device Galvanic isolation IN3 IN4 IN5 IN2 Measuring system Interface n02 n01 n03 n04 n05 R 100...

Page 261: ...from other signals Input signals voltage levels logical LOW state logical HIGH state Uin 1V Uin 4V Uin 1V Uin 4V Uin 1V Uin 4V 261 D16 16 Digital inputs n08 n09 n10 n11 n12 n04 n05 n06 n07 n01 n02 n0...

Page 262: ...bit groups IN9 IN10 1 byte IN11 16 single bits IN1 IN16 four 4 bit groups IN17 IN20 1 integer IN21 24 single bits IN1 IN24 six 4 bit groups IN25 IN30 1 integer IN31 Sampling frequency 3kHz 3kHz 3kHz...

Page 263: ...ted from the other signals Terminal description Inp n 1 Inp n 2 counting inputs pulse Prg n programmable inputs Res n reset inputs COM n common inputs n 1 2 Inp n 1 Inp n 2 counting inputs pulse Prg n...

Page 264: ...4V about 6mA 10V about 14mA 24V about 6mA 10V Insulation strength between individual measurements inputs 2kV 2kV Protection 50mA auto reset fuse 50mA auto reset fuse Isolation strength between interna...

Page 265: ...99 141 Fig 8 20 Internal structure of the optoisolated Universal counters modules 265 Inp11 Inp12 Prg1 Res1 COM 1 COM 2 3 4 R 1 4k R 1 4k R 1 4k R 1 4k F 50mA F 50mA F 50mA F 50mA Inp21 31 41 Inp22 3...

Page 266: ...ble inputs COM n common inputs n 1 2 3 4 Input signals voltage levels logical LOW state logical HIGH state Uin 1V Uin 10V Uin 1V Uin 10V Max input frequency 1kHz 1kHz Max input voltage 30V 30V Input c...

Page 267: ...0mA auto reset fuse 50mA auto reset fuse Isolation strength between internal circuits and measurements inputs 1 min 500V AC 1 min 500V AC Weight 28g 32 3g Tab 8 20 Technical data for the HM2 and HM4 m...

Page 268: ...5 n06 n07 n08 n09 n10 n11 n12 n13 n14 n15 n16 n17 n18 n19 n20 S8 8 SSR outputs OUT1 10 24V DC OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 GND n01 n02 n03 n04 n05 n06 n07 n08 n09 n10 S24 24 SSR outputs n08 n09...

Page 269: ...tection while powered internally while powered externally Internal fuse 50mA Internal fuse 500mA Internal fuse 50mA per group Internal fuse 500mA per group Internal fuse 50mA per group Internal fuse 5...

Page 270: ...conds then Pulse duty factor resolution is full 15 bits 6 56 5kHz 32768 levels PWM output quantization 20 s Tab 8 21 Technical data for the module S8 S16 and S24 Fig 8 24 Internal structure of the SSR...

Page 271: ...99 141 Fig 8 26 Internal structure of the SSR output module 24 outputs 271 F 100mA Interface Driver OUT 1 8 F 500mA Vcc 1 OUT 1 8 GND Main board 10V F 100mA F 500mA Vcc 2 Driver OUT 9 16 OUT 9 16 GND...

Page 272: ...n12 n19 n20 n21 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT9 OUT10 OUT7 OUT8 OUT11 OUT12 R65 6 relay outputs 5A 250V n01 n02 n03 n04 n05 n06 n07 n08 n09 n10 n11 n12 n13 n14 n15 n16 n17 n18 OUT1 OUT2 OUT3 OUT4 O...

Page 273: ...s j 1 resistive load 1A cos j 1 resistive load Max voltage switched by relay 250V AC 250V AC 250V AC 250V AC Isolation strength between relays 1 min 630V AC 1 min 630V AC 1 min 630V AC 1 min 630V AC I...

Page 274: ...current output OUT 6 PASSIVE OUT 5 PASSIVE OUT4 PASSIVE OUT 3 PASSIVE n05 n06 n03 n04 n01 n02 n07 n08 n09 n10 n11 n12 OUT 2 PASSIVE OUT 1 PASSIVE IO4 4 current output n05 n06 n03 n04 n01 n02 n07 n08 O...

Page 275: ...te when the device is off 27 4mA 27 4mA 27 4mA 27 4mA Output voltage dropout max 9V max 9V max 9V max 9V Overload protection Internal resettable fuse 50mA Internal resettable fuse 50mA Internal resett...

Page 276: ...4 SERVICE 24V DC 5 Imax 200mA digital input 0 15 24V DC RS 485 GND GND A B isolated IO4 4 current output n05 n06 n03 n04 n01 n02 n07 n08 OUT 4 PASSIVE OUT 3 PASSIVE OUT 2 PASSIVE OUT 1 PASSIVE Ammeter...

Page 277: ...2 Internal structure of the Passive current outputs module 277 Main board Interface Isolation Out 4 20mA Current regulator Out 4 20mA Current regulator Out 4 20mA Current regulator Out 4 20mA Current...

Page 278: ...tion USB host max current output 100mA USB host max current output 100mA USB host max current output 100mA Baudrate RS 485 bit sec 1200 2400 4800 9600 19200 38400 57600 115200 RJ 45 ETH 10Mb sec USB h...

Page 279: ...lly the printer is equipped with sensor which detects paper presents and open paper container 8 16 2 Technical data Power supply voltage 20 30 V DC 15 25 V AC 50 60 Hz External fuse 3 15 A FF 5x20 mm...

Page 280: ...n Printer ON Slow flashing Paper end Fast flashing Heading over temperature or power supply voltage incorrect 2 Paper roll compartment opening key printer serves 57 mm width paper Correct paper replac...

Page 281: ...devices serves USB port This port along with power supply connector and fuse socket are placed on back panel of the housing Paper replacement procedure 1 Press button on the front panel of the printe...

Page 282: ...User Manual For CONTROLLER DATA RECORDER MultiCon CMC 99 141 3 Place new paper roll 4 Grasp paper end so that it stick out the printer latch the cover the user should hear latching cover 282...

Page 283: ...AC instead 24 V DC see Chapter 8 16 2 Technical data can be one of causes of blown fuse and when the fuse is blown it should be replaced To replace the fuse 1 Disconnect power supply from the device 2...

Page 284: ...User Manual For CONTROLLER DATA RECORDER MultiCon CMC 99 141 Fig 8 35 Back panel view 284 Power supply USB mini USB type B Fuse...

Page 285: ...d of the file is an end of line character despite its possible presence If not stated otherwise all dates are stored in the following format 24 hour clock YYYY MM DD hh mm ss zzz where YYYY year MM mo...

Page 286: ...abel ON is ON label OFF is OFF channel HI state is set to 10 and LO state to 0 precision is 0 00 two decimal digits When viewing the data in a text editor do not be fooled by the apparent different nu...

Page 287: ...p_settings group settings of this log This is one line in following format group index name date when this log was created date when this log was ended or text NULL if log is one of the current log lo...

Page 288: ...point text representation of sample value for the first logged channel floating point text representation of sample value for the N th logged channel How to calculate the precise sample time To calcu...

Page 289: ...out the device contains dev_type type of the device serial_no serial number of the device s_version software version h_version reserved db_version reserved File log db_group_settings settings of regis...

Page 290: ...an_conf file describing settings of logged channels This file contains as many rows as channels in logged group 1 logical channel number starting from 0 2 channel name 3 channel source mode 4 displaye...

Page 291: ...es with samples partX db_ These files contains a logged samples Names of these files are created according to a rule partX db_SUFFIX where X unique identifier of a file see log db_log_files SUFFIX can...

Page 292: ...tX db_timestamp file view example If file has suffix samples then it contains logged samples 1 IDS unique hexadecimal id of sample in log 2 7 floating point value of logged channel in a group see file...

Page 293: ...s serial number does not exist then it is created 2 in such directory files witch information about logs are created description bellow 3 each log is stored in a separate subdirectory Files hierarchy...

Page 294: ...query like http IP_address cgi bin data cgi cmd command id_first 123 id_last 321 additional parameters Format of the id_first and id_last Numbers can be given to each parameter in decimal or hexadecim...

Page 295: ...rned example requesting list of logs but there was no logs on device or given boundaries are outside available ID range the blank page will be returned If valid data query is performed but data reques...

Page 296: ...l settings Example of viewing list of log files in log gX_YYYY_MM_DD_hh_mm_ss use this query syntax http IP_address cgi bin data cgi cmd log log_name gX_YYYY_MM_DD_hh_mm_ss file log_files Obtaining re...

Page 297: ...User Manual For CONTROLLER DATA RECORDER MultiCon CMC 99 141 297...

Page 298: ...User Manual For CONTROLLER DATA RECORDER MultiCon CMC 99 141 298...

Page 299: ...User Manual For CONTROLLER DATA RECORDER MultiCon CMC 99 141 299...

Page 300: ...SIMEX Sp z o o ul Wielopole 11 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Reviews: