Defining Parameters
5-28
FM 353 Stepper Drive Positioning Module
6ES7 353-1AH01-8BG0
Loading the SDB in the CPU
When you have created the SDB, you must load the “system data” of the project
into the CPU.
There are two ways of proceeding:
Method 1
Select the online window in the
SIMATIC Manager
(the online and offline win-
dows must be open)
Copy the system data from the offline project in
CPU\S7-Program\Blocks\Sys-
tem data
into the online project (drag with the mouse or select Copy/Paste).
Method 2
Select the system data in the
SIMATIC Manager
in
CPU\S7-Pro-
gram\Blocks\System data
.
Activate the menu
Target system > Load
(or the right mouse button) to load
the system data into the CPU
or
Use the menu
Target system > Load in EPROM memory card on CPU
You can also program the memory card for the CPU on a programming device/PC.
If the configuration is loaded from HW-CONFIG, this SDB is
not
loaded into the
CPU.
Deleting SDBs in the CPU
To delete the SDBs in the CPU:
1. Select “Parameterize FM 353”.
2. Select menu
File > Display SDB
. Delete the SDB(s).
3. Close “Parameterize FM 353” and in the
SIMATIC Manager
in Online Project
select CPU\S7-Progam\Blocks\System data
. Delete the system data.
4. Transfer the system data to the CPU again (see above)
J
Summary of Contents for SIMATIC FM 353
Page 22: ...Product Overview 1 12 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...
Page 32: ...Installing and Removing 3 6 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...
Page 282: ...Description of Functions 9 82 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...
Page 354: ...User Data Block AW DB B 16 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...