Programming the Technological Functions
6-64
FM 353 Stepper Drive Positioning Module
6ES7 353-1AH01-8BG0
6.8
Error list, system messages (CPU)
The Table below lists some of the errors which occur during data transfer with the
internal SFC/SFBs (RET_VAL in SFCs 51, 58 and 59 and status messages (bytes
2 and 3), SFB 52/53, system messages) (see Reference Manual
System Software
for S7-300/400; System and Standard Functions
).
Table 6-12
Error list
Error Code (AW-DB, DBW66)
Description
HEX
DEC
INT
0
0
0
No errors
8082
32898
−
32638
SZL_ID invalid or not in CPU
8085
32901
−
32635
Information currently unavailable (caused by system)
80A0
32928
−
32608
Negative acknowledgement when reading from module. Module re-
moved during Read operation or module defective.
80A1
32929
−
32607
Negative acknowledgement while writing to module. Module removed
during Write operation or module defective.
80A2
32930
−
32606
DP protocol error in layer 2 (data transfer over Profibus-DP interrupted,
e.g. due to wirebreak, missing terminator, parameterization error, etc.)
80A3
32931
−
32605
S
PROFIBUS: DP protocol error in layer 2 (data transfer over Profi-
bus-DP interrupted, e.g. due to wirebreak, missing terminator,
parameterization error, etc.)
S
PROFINET IO: General CM error
80A4
32932
−
32604
Communication problem on K bus
80A7
32935
−
63601
DP slave or module is busy
80A9
32937
−
63599
This function is not supported by DP slave or by the module.
80AA
to
80AF
32938
to
32943
−
32598
to
−
32593
DP slave or module is reporting a manufacturer
−
specific error in the
evaluation. For specifying the error, please refer to the Manufacturer
Documentation of the DP slave or of the module.
80B0
32944
−
32592
The module does not know this data record.
80B1
32945
−
32591
Invalid length specification in the RECORD parameter
80B2
32946
−
32590
The configured slot is not occupied.
80B3
32947
−
32589
Actual module type not the same as setpoint module type
80B5
32949
−
32587
DP slave or module not ready
80B6
32950
−
32586
Access to DP slave or module denied
80C0
32960
−
32576
Module does not yet have the data to be read available
80C1
32961
−
32575
Data from an identical Write job have not yet been processed on the
module
80C2
32962
−
32574
Module is currently servicing the maximum possible number of re-
quests
80C3
32963
−
32573
Needed resources (such as memory, etc.) are currently in use
Summary of Contents for SIMATIC FM 353
Page 22: ...Product Overview 1 12 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...
Page 32: ...Installing and Removing 3 6 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...
Page 282: ...Description of Functions 9 82 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...
Page 354: ...User Data Block AW DB B 16 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...