Starting up
7-2
FM 353 Stepper Drive Positioning Module
6ES7 353-1AH01-8BG0
7.1
Installation and wiring
Installation information
You can find information about how to install your module:
S
S
In the manual
S7-300 Programmable Controller, Hardware and Installation
Wiring information
You can find information about how to wire your module:
S
S
In the manual
S7-300 Programmable Controller, Hardware and Installation
Checklist
The checklist below will help you check important steps in the installation and para-
meterization of the FM 353 positioning module.
Table 7-1
Installation and wiring checklist
Step
Check
What to do:
OK
1
Slots
Plug the module into one of the suitable slots.
2
Shielding
Check the shielding of the FM 353 positioning module:
S
To ensure proper shielding, the module must be screwed down
firmly on the rail.
S
The shielding for shielded lines for digital I/O modules must be
connected to the shielding terminal element.
S
The shielding for the setpoint cable should not be grounded on
the drive-unit end.
3
Limit switches
Check the start/stop limit switches. The limit-switch connections must
be connected to the power section. The start/stop limit switches
should not be connected to the digital inputs.
4
Parameterize
Make sure the FM 353 positioning module setup is consistent with
the parameterization. Check in particular that the wiring of the digital
I/O modules matches the machine data.
Summary of Contents for SIMATIC FM 353
Page 22: ...Product Overview 1 12 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...
Page 32: ...Installing and Removing 3 6 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...
Page 282: ...Description of Functions 9 82 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...