Advanced commissioning
7.4 Drive control via PROFIBUS and PROFINET
SIMATIC ET 200pro FC-2 converter
104
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
Data block
Byte n
Bytes n + 1
n
Values, parameter 1
Format
02 hex
: Integer8
03 hex
: Integer16
04 hex
: Integer32
05 hex
: Unsigned8
06 hex
: Unsigned16
07 hex
: Unsigned32
08 hex
: FloatingPoint
0A hex
: OctetString
0D hex
: TimeDifference
34 hex
: TimeOfDay without date indication
35 hex
: TimeDifference with date indication
36 hex
: TimeDifference without date indication
41 hex
: Byte
42 hex
: Word
43 hex
: Double word
44 hex
: Error
Number of index values or - for a negative
response - number of error values
4
Value of the 1st index or - for a negative response - error value 1
You can find the error values in a table at the end of this section.
6
…
…
Values, parameter 2
…
…
…
Values, parameter m
…
Changing parameter values
Table 7- 6
Request to change parameters
Data block
Byte n
Bytes n + 1
n
Header
Reference
00 hex ... FF hex
02 hex: Change request
0
01 hex (ID of drive objects, at G120 al-
ways = 1)
Number of parameters (m)
01 hex ... 27 hex
2
Address, parameter 1 10 hex: Parameter value
Number of indices
00 hex ... EA hex
(00 hex and 01 hex are equivalents)
4
Parameter number
0001 hex ... FFFF hex
6
Number of the 1st index
0001 hex ... FFFF hex
8
…
…
Address, parameter 2 …
…
…
…
Address, parameter m …