Alarms, faults and system messages
10.5 Faults, alarm buffer and alarm history
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
237
Parameters of the fault buffer and the fault history
Parameter
Description
r0945
Fault code
Displays the numbers of the faults that have occurred
r0948
Fault time received in milliseconds
Displays the time in milliseconds when the fault occurred
r0949
Fault value
Displays additional information about the fault
p0952
Fault cases, counter
A fault case can contain one or several faults.
Number of fault cases that have occurred since the last acknowledgement. With
p0952 = 0 you delete the fault buffer and the fault history.
r2109
Fault time removed in milliseconds
Displays the time in milliseconds when the fault occurred
r2130
Fault time received in days
Displays the time in days when the fault occurred
r2131
Actual fault code
Displays the code of the oldest fault that is still active
r2133
Fault value for float values
Displays additional information about the fault that occurred for float values
r2136
Fault time removed in days
Displays the time in days when the fault was removed
Extended settings for faults
Parameter
Description
p2100[0 … 19] Setting the fault number for fault response
Selecting the faults for which the fault response should be changed.
You can modify the motor fault response for up to 20 different fault codes.
p2101[0 … 19] Setting, fault response
Setting the fault response for the selected fault
p2118[0 … 19] Setting the message number for the message type
Selection of the message for which the message type should be changed.
You can change up to 20 different faults into an alarm, or suppress faults:
p2119[0 … 19] Setting the message type
Setting the message type for the selected fault
1: Fault
2: Alarm
3: No message