Alarms, faults and system messages
10.6 List of alarms and faults
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
239
Table 10- 1 The most important alarms and faults
Number Cause
Remedy
F01000
Software error in the CU
Replace CU.
F01001
Floating point exception
Switch off CU and switch on again.
F01015
Software error in the CU
Upgrade firmware or contact technical support.
F01018
Power-up aborted more than once 1.
Switch the module off and on again.
2.
After this fault has been output, the module is booted with the factory
settings.
3.
Recommission the inverter.
A01028
Configuration error
Explanation: Parameterization on the memory card has been created with
a different type of module (article number).
Check the module parameters and recommission if necessary.
F01033
Switching over units: Reference
parameter value invalid
Set the value of the reference parameter not equal to 0.0 (p0304, p0305,
p0310, p0596, p2000, p2001, p2002, p2003, r2004).
F01034
Switching over units: Calculation of
the parameter values after refer-
ence value change unsuccessful
Select the value of the reference parameter so that the parameters in-
volved can be calculated in the per unit notation (p0304, p0305, p0310,
p0596, p2000, p2001, p2002, p2003, r2004).
F01040
Parameters must be saved
Save parameters (p0971).
Switch CU off and on again.
F01044
Error when loading data from
memory card
Replace memory card or CU.
A01101
Memory card not available
Insert a memory card or deactivate the warning A01101.
Spare parts and accessories (Page 29)
F01105
CU: Insufficient memory
Reduce number of data records.
F01205
CU: Time slice overflow
Contact technical support.
F01250
CU hardware fault
Replace CU.
F01512
An attempt has been made to
establish a conversion factor for
scaling which does not exist
Create scaling or check transfer value.
A01590
Motor maintenance interval lapsed Carry out maintenance and reset the maintenance interval (p0651).
F01600
STOP A initiated
Select STO and then deselect again.
F01650
Acceptance test required
Carry out an acceptance test and create acceptance certificate.
Switch off the Control Unit and switch on again.
F01659
Write task for parameter rejected
Cause: The inverter should be reset to the factory setting. However, it is
not permissible to reset the safety functions as the safety functions are
currently enabled.
Remedy with operator panel:
p0010 = 30
Parameter reset
p9761 = …
Enter password for the safety functions.
p0970 = 5
Reset start safety parameter.
The inverter sets p0970 = 5 once it has reset the parame-
ters.
Then reset the inverter to the factory setting again.
F01662
CU hardware fault
Switch CU off and on again, upgrade firmware or contact technical sup-
port.