Repair
9.3 Firmware upgrade and downgrade
SIMATIC ET 200pro FC-2 converter
222
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
16. Reconnect all connectors.
17. Take your settings over from your data
backup to the inverter.
Transferring the settings from the
memory card (Page 195)
You have updated the inverter's firmware to an older version and have adopted your saved
settings in the inverter.
❒
9.3.3
Correcting a failed firmware upgrade or downgrade
How does the converter report a failed upgrade or downgrade?
The converter signals a failed firmware up-
grade or downgrade with a quickly flashing
RDY LED and a lit up BF LED.
Correcting a failed upgrade or downgrade
To correct a failed firmware upgrade or downgrade you can check the following:
●
Does the firmware version fulfill the requirements of your converter?
–
For an upgrade at least V4.7.x.
–
For a downgrade at least V4.7.
●
Have you inserted the card properly?
●
Does the card contain the correct firmware?
●
Repeat the appropriate procedure.