Advanced commissioning
7.6 Selecting physical units
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
115
An overview of the unit groups and the possible physical units can also be found in the List
Manual.
7.6.3
Technological unit of the technology controller
Options when selecting the technological unit
p0595 defines in which technological unit the input and output variables of the technology
controller are calculated, e.g. [bar], [m³/min] or [kg/h].
Reference variable
p0596 defines the reference variable of the technological unit for the technology controller.
Unit group
Parameters involved with p0595 belong to unit group 9_1.
Further information on this topic is provided in the List Manual.
Manuals for your inverter (Page 272)
Special features
You must optimize the technology controller after changing p0595 or p0596.
7.6.4
Setting the system of units and technology unit
Precondition
STARTER must be in the offline mode to switch over the units.
Select the online mode or the offline mode
using the adjacent buttons.
STARTER indicates whether you change the settings online in the converter or offline in the
PC:
/
.