Advanced commissioning
7.9 Setpoint calculation
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
141
7.9.5
Speed limitation
The maximum speed limits the speed setpoint range for both directions of rotation.
The converter generates a message (fault or alarm) when the maximum speed is exceeded.
If you must limit the speed depending on the direction of rotation, then you can define speed
limits for each direction.
Table 7- 21 Parameters for the speed limitation
Parameter
Description
p1082
Maximum speed (factory setting: 1500 rpm)
p1083
Speed limit, positive direction of rotation (factory setting: 210,000 rpm)
p1085
CI: Speed limit, positive direction of rotation (factory setting: 1083)
p1086
Speed limit, negative direction of rotation (factory setting: -210,000 rpm)
p1088
CI: Speed limit, negative direction of rotation (factory setting: 1086)
7.9.6
Ramp-function generator
The ramp-function generator in the setpoint channel limits the rate change of the speed
setpoint (acceleration). A reduced acceleration reduces the accelerating torque of the motor.
As a consequence, the motor reduces the stress on the mechanical system of the driven
machine.
The extended ramp-function generator not only limits the acceleration, but by rounding the
setpoint, also acceleration changes (jerk). This means that the motor does not suddenly
generate a torque.