Advanced commissioning
7.4 Drive control via PROFIBUS and PROFINET
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
101
Status word 1 (ZSW1)
Status word 1 (bits 0-10 in accordance with PROFIdrive profile, bits 11-15 specific to the
inverter).
Bit Significance
Comments
Signal interconnec-
tion in the inverter
0
1 = Ready to start
Power supply switched on; electronics initialized; pulses locked.
p2080[0] = r0899.0
1
1 = Ready
Motor is switched on (ON/OFF1 = 1), no fault is active. With the com-
mand "Enable operation" (STW1.3), the inverter switches on the motor.
p2080[1] = r0899.1
2
1 = Operation ena-
bled
Motor follows setpoint. See control word 1, bit 3.
p2080[2] = r0899.2
3
1 = Fault active
The inverter has a fault. Acknowledge fault using STW1.7.
p2080[3] = r2139.3
4
1 = OFF2 inactive
Coast down to standstill is not active.
p2080[4] = r0899.4
5
1 = OFF3 inactive
Quick stop is not active.
p2080[5] = r0899.5
6
1 = Closing lockout
active
It is only possible to switch on the motor after an OFF1 followed by ON. p2080[6] = r0899.6
7
1 = Alarm active
Motor remains switched on; no acknowledgment is necessary.
p2080[7] = r2139.7
8
1 = Speed deviation
within the tolerance
range
Setpoint / actual value deviation within the tolerance range.
p2080[8] = r2197.7
9
1 = Master control
requested
The automation system is requested to accept the inverter control.
p2080[9] = r0899.9
10 1 = Comparison
speed reached or
exceeded
Speed is greater than or equal to the corresponding maximum speed.
p2080[10] =
r2199.1
11 0 = I, M or P limit
reached
Comparison value for current, torque or power has been reached or
exceeded.
p2080[11] =
r1407.7
12 1 = Holding brake
open
Signal to open and close a motor holding brake.
p2080[12] =
r0899.12
13 0 = Alarm, motor
overtemperature
---
p2080[13] =
r2135.14
14 1 = Motor rotates
clockwise
Internal inverter actual value > 0
p2080[14] =
r2197.3
0 = Motor rotates
counterclockwise
Internal inverter actual value < 0
15 0 = Alarm, inverter
thermal overload
---
p2080[15] =
r0836.0 / r2135.15
7.4.1.2
Extend telegram
The converter interconnects the corresponding signals with the fieldbus interface. Generally,
the interconnections are protected so that they cannot be changed. With the appropriate
converter settings, these interconnections can be changed.
Extend telegram
The telegram can be extended, by "attaching" additional signals.