Advanced commissioning
7.19 PROFIenergy profile for PROFINET
SIMATIC ET 200pro FC-2 converter
188
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
7.19.3
Control commands and status queries
PROFIenergy control commands
●
Start_Pause
Dependent on the pause duration, switches into the energy-saving mode.
–
For p5611.2 = 0, from operating states S1 (switching on inhibited) or S2 (ready to
switch on)
–
For p5611.2 = 1, also from operating states S3 (ready) or S4 (operation).
●
Start_Pause_with_time_response
Dependent on the pause duration switches into the energy-saving mode and also
specifies the transition times in the command response.
–
For p5611.2 = 0, from operating states S1 (switching on inhibited) or S2 (ready to
switch on)
–
For p5611.2 = 1, also from operating states S3 (ready) or S4 (operation).
●
End_Pause
Switches from energy-saving mode to the operating state.
Cancels the switching from the operating state to the energy-saving mode.
PROFIenergy status requests
●
List_Energy_Saving_Modes
Determines all supported energy-saving modes.
●
Get_Mode
Determines information about the selected energy-saving mode.
●
PEM_Status
Determines the current PROFIenergy status.
●
PEM_Status_with_CTTO
Determines the current PROFIenergy status, such as the PEM_Status, together with the
regular transition time to the operating state.
●
PE_ldentify
Determines the supported PROFIenergy commands.
●
Query_Version
Shows the implemented PROFIenergy profile.
●
Get_Measurement_List
This command returns the measured value IDs that can be accessed using the
"Get_Measurement_Values" command.
●
Get_Measurement_List_with_object_number
This command returns the measured value IDs and the associated object number that
can be accessed using the "Get_Measurement_Values_with_object_number" command.