SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
245
Technical data
11
11.1
Technical data
Technical data
General technical data and information about the mechanical and climatic environmental
condition of the ET 200pro system is provided in the "SIMATIC ET 200pro Distributed I/O
System" manual.
Note
Deviating from this general technical data, for the ET 200pro FC-2 inverter, the following
applies:
Drop test (in original package)
≤
0.35 m.
Table 11- 1 Technical data
Date
Unit
Value
Rated input voltage
V
AC 400
Permissible voltage range min.
V
AC 380
Permissible voltage range max.
V
AC 480
Rated output current
@ 45 °C
A
3.9
@ 55 °C
A
3.5
Maximum output current (3 s)
A
2 x rated output current
Rated input current 3AC
A
3.7
Integrated device fuse
A
16, medium time-lag
Rated power @ 55 °C
kW
1.10
Power with overload (150% for 60 s every 300 s)
kW
1.65
Power with overload (200% for 3 s every 300 s)
kW
2.20
Power without overload capability
kW
1.20
Integrated brake control
V
DC 200
Maximum current of the brake control
A
1.0
Pulse frequency (factory setting)
kHz
4
Installation altitude above sea level
m
2000
Efficiency
η
%
95 … 97
Power factor
---
0.9
Mechanical data