Advanced commissioning
7.8 Setpoints
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
133
Figure 7-17 Function chart of the motorized potentiometer
Example
Setting with the motorized potentiometer as setpoint source:
Parameter
Description
p1070 = 1050
Interconnects the main setpoint with the motorized potentiometer output.
Parameter
Table 7- 15 Basic setup of motorized potentiometer
Parameter
Description
Setting
p1035[0…n]
BI: Motorized potentiometer
setpoint higher
Signal source to continuously increase the setpoint
The factory setting depends on the inverter.
Inverters with PROFIBUS or PROFINET interface:
[0] 2090.13
[1] 0
Inverters without PROFIBUS or PROFINET interface: 0
p1036[0…n]
BI: Motorized potentiometer
setpoint lower
Signal source to continuously decrease the setpoint
The factory setting depends on the inverter.
Inverters with PROFIBUS or PROFINET interface:
[0] 2090.14
[1] 0
Inverters without PROFIBUS or PROFINET interface: 0
p1040[0…n]
Motorized potentiometer
start value [rpm]
Start value that is effective when the motor is switched on.
Factory setting: 0 rpm
p1047
MOP ramp-up time [s]
MOP ramp-up time
Factory setting: 10 s