A.4 Acceptance tests for the safety functions
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
269
Status
•
The inverter signals neither faults nor alarms of the safety
functions (r0945[0…7], r2122[0…7]).
•
The inverter signals the following:
"STO is selected" (r9773.0 = 1).
"STO is active" (r9773.1 = 1).
4.
Deselect STO
4.1.
Deselect STO.
4.2.
Check the following:
•
STO is not active (r9773.1 = 0).
•
The inverter signals neither faults nor alarms of the safety
functions (r0945[0…7], r2122[0…7]).
You have performed the acceptance test of the STO function.
❒
A.4.3
Machine documentation
Machine or plant description
Designation
Type
Serial number
Manufacturer
End customer
Overview diagram of the machine and/or system:
Inverter data
The inverter data include the hardware version of the safety-relevant inverter.
Labeling the drive
Article number and hardware version of the inverter