Advanced commissioning
7.4 Drive control via PROFIBUS and PROFINET
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
105
Data block
Byte n
Bytes n + 1
n
Values, parameter 1
Format
02 hex:
Integer 8
03 hex:
Integer 16
04 hex:
Integer 32
05 hex:
Unsigned 8
06 hex:
Unsigned 16
07 hex:
Unsigned 32
08 hex:
Floating Point
0A hex:
Octet String
0D hex:
Time Difference
34 hex
: TimeOfDay without date indication
35 hex
: TimeDifference with date indication
36 hex
: TimeDifference without date indication
41 hex:
Byte
42 hex:
Word
43 hex:
Double word
Number of index values
00 hex ... EA hex
Value of the 1st index
…
Values, parameter 2
…
…
…
Values, parameter m
…
Table 7- 7
Response, if the inverter has executed the change request
Data block
Byte n
Bytes n + 1
n
Header
Reference (identical to a change request)
02 hex (change request successful)
0
01 hex (ID of drive objects, at G120 al-
ways = 1)
Number of parameters (identical to a change
request)
2
Table 7- 8
Response if the inverter was not able to completely execute the change request
Data block
Byte n
Bytes n + 1
n
Header
Reference (identical to a change request)
82 hex: (Inverter was not able to completely
execute the write request)
0
01 hex (ID of drive objects, at G120 al-
ways = 1)
Number of parameters (identical to a change
request)
2
Values, parameter 1
Format
40 hex: Zero (change request for this data
block executed)
44 hex: Error (change request for this data
block not executed)
Number of error values
00 hex
01 hex or 02 hex
4
Only for "Error" - error value 1
You can find the error values in the table at the end of this section.
6
Only for "Error" - error value 2
Error value 2 is either zero, or it contains the number of the first index where the error oc-
curred.
8
Values, parameter 2
...