Advanced commissioning
7.19 PROFIenergy profile for PROFINET
SIMATIC ET 200pro FC-2 converter
186
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
Table 7- 34 Efficiency optimization, method 1
Parameter
Description
Setting
p1570
Flux setpoint [%]
Factory setting: 100 %
p1580
Efficiency optimization [%]
0 %: Efficiency optimization is deactivated.
100 %: In no-load operation, the inverter reduces the flux setpoint to
50% of the rated motor flux.
The factory setting depends on the inverter.
7.19
PROFIenergy profile for PROFINET
PROFIenergy is an energy management standard for production plants, based on the
PROFINET communication protocol. The functionality is certified and described in the
PROFIenergy profile of the PNO.
The control transfers the PROFIenergy commands in acyclic operation to the inverter in data
set 80A0 hex.
The inverters support the PROFIenergy profile V1.1 and the function unit class 3.
Parameters r5600 to p5614 are reserved for PROFIenergy functions in the inverter.
An application example for energy savings with PROFIenergy is available in the Internet at:
PROFIenergy - saving energy with SIMATIC S7
https://support.industry.siemens.com/cs/ww/en/view/41986454
7.19.1
General inverter behavior when in the PROFIenergy energy-saving mode
●
When the PROFIenergy energy-saving mode is active, the inverter issues alarm A08800.
●
When the PROFIenergy energy-saving mode is active, the inverter does not send any
diagnostic alarms.
●
If the bus connection to the control system is interrupted while the inverter is in the
energy-saving mode, the inverter exits the energy-saving mode and resumes normal
operation.
●
The inverter changes into normal operation if the control system goes into the stop
condition while the inverter is in the energy-saving mode.
PROFIenergy energy-saving mode 2
Parameter r5600 shows the active PROFIenergy energy-saving mode.
Connector parameter r5613 indicates whether the PROFIenergy energy-saving mode is
active. You can set additional responses using these parameters.