Appendix
A.4 Acceptance tests for the safety functions
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
267
Where can you find additional information?
●
This manual suffices for assigning a different meaning to the digital inputs.
●
The parameter list in the List Manual is sufficient for more complex signal
interconnections.
●
The function diagrams in the List Manual provide a complete overview of the factory
setting for the signal interconnections and the setting options.
A.4
Acceptance tests for the safety functions
A.4.1
Recommended acceptance test
The following descriptions for the acceptance test are recommendations that illustrate the
principle of acceptance. You may deviate from these recommendations if you check the
following once you have completed commissioning:
●
Correct assignment of the interfaces of each converter with the safety function:
–
Fail-safe inputs
–
PROFIsafe address
●
Correct setting of the STO safety function.
Note
Perform the acceptance test with the maximum possible velocity and acceleration in
order to test the expected maximum braking distances and braking times.
Note
Non-critical alarms
The following alarms are issued following each system ramp-up and are not critical for
acceptance:
•
A01697
•
A01796