Alarms, faults and system messages
10.6 List of alarms and faults
SIMATIC ET 200pro FC-2 converter
244
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
Number Cause
Remedy
F30022
Power Module: Monitoring U
CE
Check or replace Power Module.
F30027
Time monitoring for DC link pre-
charging
Check the supply voltage at the input terminals.
Check the line voltage setting (p0210).
F30035
Overtemperature, intake air
•
Check whether the fan is running.
•
Check the fan filter elements.
•
Check whether the ambient temperature is in the permissible range.
F30036
Overtemperature, inside area
F30037
Rectifier overtemperature
See F30035 and, in addition:
•
Check the motor load.
•
Check the line phases
A30049
Internal fan defective
Check the internal fan and if required replace.
F30052
Incorrect Power Module data
Replace Power Module or upgrade CU firmware.
F30053
Error in FPGA data
Replace the Power Module.
F30059
Internal fan defective
Check the internal fan and if required replace.
A30502
DC link overvoltage
•
Check the unit supply voltage (p0210).
•
Check the dimensioning of the line reactor.
F30600
STOP A initiated
Select STO and then deselect again.
F30662
CU hardware fault
Switch CU off and on again, upgrade firmware or contact technical sup-
port.
F30664
CU power up aborted
Switch CU off and on again, upgrade firmware or contact technical sup-
port.
F30850
Software error in the Power Mod-
ule
Replace Power Module or contact technical support.
A30920
Temperature sensor fault
Check that the sensor is connected correctly.
For further information, please refer to the List Manual.