6.2 Drive functions
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
System Manual, 06/2016, A2B00096162-AN
53
6.2.15
Cord-operated switch
Description of function
The cord-operated switch command has the same function as the GATE OPEN command.
However, it also offers the option of partial opening. "Opening width in percent" and "Hold-
open time cord operated switch" can be set in the Special parameters menu. The cord-
operated switch command remains present until a new input signal is activated or the "Hold-
open time cord operated switch" expires.
Connection
The "Nudge" function is connected to "Input 2" (X6). See also Section Digital input signals
(Page 131).
Signals
Signal
Description
1 (voltage applied)
The cord-operated switch command is present and the door opens
0 (voltage not applied)
The cord-operated switch command is not present and the door
closes