Controllers
6.10 Communication to PROFINET
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
System Manual, 06/2016, A2B00096162-AN
193
6.10.2
Configuration
The resulting configuration data is in the GSD file (see Table 6-28 GSD files (Page 150)).
The structure expected by the PROFINET module is described below (for informational
purposes only):
Table 6- 57 PROFINET configuration data
Slot
Api
Subslot
Module ID Submodule ID Description
0
0
0001
hex
1
1
DAP (ATD430W)
0
0
8000
hex
1
2
Interface
0
0
8001
hex
1
3
Port 1
0
0
8002
hex
1
3
Port 2
1
0
0001
hex
28
hex
1
22 bytes IO (4 words of PKW and 7 words of
PZD are mapped)
6.10.3
Diagnostics
The internal communication bus between the SIDOOR controller and the communication
module is monitored by the master driver of the communication module (PROFINET
module). A PROFINET diagnostic alarm is triggered if communication is interrupted or
quality becomes too poor. This diagnostic alarm is then present for at least 5 seconds and is
structured as follows:
Table 6- 58 Properties of diagnostic alarm
Property of diag-
nostic alarm
Value
Slot
1
Subslot
1
Channel
1
Error ID
1B
hex
Extended channel
error type
1
Extended channel
error value
Bit
10 9 8 7 6 5 4 3 2 1 0
Telegram length (LGE) false
X
Remaining runtime exceeded
X
Block check character (BCC) false
X
Telegram start (STX) false
X
Telegram type unknown (ADR)
X
Slave address false
X
Memory overflow
X
Parity error
X
Internal error
X
Answer delay time exceeded
X
Telegram type not identical
X
Bits 15 to 11 are reserved.
Maintenance
No