boards.fm
P31003-H3560-S403-54-7620, 09/05
HiPath 3000 V6.0, HiPath 5000 V6.0, Provisional Service Manual
3-167
Boards for HiPath 3000
Peripheral Boards
AC power
100 - 240 V AC
Frequency range
47 to 63 Hz
Connected output
200 W
Output power consumption/
nominal output
140 W
Mains/nominal voltage
54.2 V
UPS batteries
V39113-W5123-E891
Four batteries are supplied
built-in.
V39113-W5123-E891
Batteries are not included in
the scope of supply and must
be ordered separately.
Battery operation:
●
Permitted batteries
Manufacturer/type num-
ber
●
Number of batteries
●
Size (Ah)
●
Nominal voltage
●
Overload protection
●
CSB/EVX-1270, Hitachi/HP6.5-12, Yuasa/NP6-12, Varta/
Noack 43720303, Sonnenschein/0719143200, Panasonic/
LCR12-7P
●
4 units, 12 V each
●
7 Ah
●
48 V (fully charged 54 V, discharge to 44 V)
●
Melting fuse 5 x 20 mm, 2.5
A/slow-blowing
Nominal current
2.5 A
Overload protection
Electronic current limiting circuit
Ambient temperature
In buildings, +5 to +45 °C (41 to 113 °F)
Humidity
95%, non-condensing
Cooling
Natural convection
Protection
IP 21 (DIN 40050)
Housing dimensions (W x D
x H in mm)
250 x 114 x 317
Weight
approx. 14.1 kg (incl. batteries) approx. 4.1 kg (without batter-
ies)
Symbol
CE
Personal safety, insulation
EN60950 and IEC950
Grounding, shielding
Protection class 1, output is floating against ground
Table 3-69
EPSU2 - Technical Specifications
EPSU2
S30122-K7221-X1
EPSU2
S30122-K7221-X2