6-Channel F Analog Input MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
90
A5E00482820-12
Figure 9–2 Non-Redundant FAI Interface
1
FET SWITCH
1
2
J1
FET SWITCH
1
2
6.2 V
FAI MODULE
FET SWITCH
BOARD
FAI MTA
215
O
H
M
1
2
J2
-
5.6 V
MANA
2
1
FET SWITCH
1
2
+
CURRENT
SOURCE
2
1
9.5
Installation Requirements
See Section 2,
, before performing any installation and observe all
warnings
A common interconnecting cable (6ES7922-3BD00-0AS0 or 6ES7922-3BJ00-
0AS0), supporting six analog input channels, interconnects the analog input
termination assembly to the 6-channel analog input module (6ES7 336-1HE00-
0AB0, E-Stand 4 or higher). See Figure 2-28.
It may be necessary to modify the printed circuit board as follows:
To disconnect the interconnecting cable shield from ground at the MTA only, cut
and remove the shield disconnect jumper,
W100
and
W101
, for the associated
cable.
Note
•
To separate channel input low from power supply common, cut and remove
the jumper
W200
. This will provide isolation between the all the inputs and
power return.
•
W200
should never be cut when an FAI module is connected to J1 on the
MTA. Doing so will cause the input to exceed the common mode specification
and will generate a common-mode diagnostic error.
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......