Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
229
Isolation
between channels < -- > secondary
Yes (250 VAC)
between the channels
Yes. U< =150 V reinforced insulation
U > 150 V to 250 V basic insulation
Insulation test
Rated voltage 150V < Ue < 300V
Rated voltage 100V < Ue < 150V
Test voltage (routine test at IEC 61131-2)
1350 VAC/2sec (all channels to sec. + shield)
820 VAC/2sec (between channels for 150 VDC)
Note
Fuses are available as spare parts from Siemens.
Fuse information can be found at:
http://www.littelfuse.com
http://www.bussmann.com
Relays are available as spare parts from Siemens.
Relay Information can be found at:
Summary of Contents for ET 200M