8-Channel Analog Input MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
42
A5E00482820-12
4.7
Technical Specifications
Technical Specifications for 8-Channel Analog Input MTA
(6ES7650-1AA51-2XX0 or 6ES7650-1AA50-2XX0)
Dimensions - See Section 1, Figure 1.3, Long Version
Mounting
DIN Rail
35mm (deep top hat style)
Power Input
Voltage Input for Single or Redundant Feed
21.6 to 28.8 VDC
Current Consumption (nominal ratings; all channels
connected)
Inrush
8.238 A maximum (Includes 8.16 A for
transmitter inrush)
Normal
0.265 A maximum
Terminal Block Wire Sizes
TB100 & TB101
Wire Size – US
24 – 14 gauge AWG
Wire Size – Metric
0,205 – 2,08 mm sq.
Power Supply Specifications
See Module Specs
Fuse Ratings
Individual channel – Normal
0.5 A Fast blow (Littelfuse P/N: 273.500)
(Siemens Spare P/N: A5E01568880)
Individual channel – Optional
1.5 A Fast blow (Littelfuse P/N: 273 01.5)
(Siemens Spare P/N: A5E01568886)
Max total channel current: 8.16 Amps
Module
NA
Indicators
Input Power
Green LED on when input power available
Module Power
NA
Channel Power
Green LED on when sensor power available
Field Terminal Block Wire Sizes TB1 – TB2
Wire Size – US
24 – 14 gauge AWG
Wire Size – Metric
0,205 – 2,08 mm sq.
Environmental
Ambient Temperature
-25C to +60C
Humidity
5% to 95% Non-condensing
Approvals
MTA Agency Approvals
See Preface section, Approvals Table
Note
Fuses are available as spare parts from Siemens.
Fuse information can be found at:
http://www.littelfuse.com
http://www.bussmann.com
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......