Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
222
A5E00482820-12
17.5
Maintenance
See Section 3,
, before performing any maintenance and observe all
warnings
Under normal operation, the
A/B
Power LED
and
the
Module 1/2 Fuse LED
are
on. If all are off, check the power supply to MTA. If the
A/B
Power LED
is off,
check the power supply to the MTA. If the
Module 1/2 Fuse LED
is off, check the
channel fuse and replace as necessary.
Remove field power before removing or installing any device.
!
Warning
Electrical shock hazard
•
An electrical shock hazard exists for Relay Output MTAs only when connected
to loads with voltage > 30V rms and 42.4V peak or 60V dc
•
Remove power from all wires and terminals before working on equipment.
•
For AC voltages all channels must be the same phase. For voltages greater
than 150 VDC, all channels must be of the same voltage.