8-Channel Analog Input MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
39
4.4
Installation Requirements
See Section 2,
, before performing any installation and observe all
warnings
A common interconnecting cable (6ES7922-3BD00-0AS0 or 6ES7922-3BJ00-
0AS0), supporting eight analog input channels, connects the analog input
termination assembly to the 8-channel analog input module (6ES7 331-7NF00-
0AB0, E-Stand 5 or higher). See Figure 4–1.
It may be necessary to modify the printed circuit board as follows:
•
For channels measuring voltage, move the
I – V
jumper for that channel to the
V
side.
•
For channels measuring current, move the
I – V
jumper for that channel to the
I
side
•
To separate channel input low from power supply common, cut and remove the
jumper associated with that channel, W8 for CH0 through W15 for CH7.
Note
To disconnect the interconnecting cable shield from ground at the MTA only, cut
and remove the shield disconnect jumpers,
W100
and
W101
, for the associated
cable.
4.5
Maintenance
Under normal operation, the
A/B
Power LED
and all the
Channel Fuse LEDs
are
on. If all are off, check the power supply to MTA. If the
A/B
Power LED
is off,
check the power supply to the MTA. If the
Channel Fuse LED
is off, check the
channel fuse and replace if necessary.
See Section 3,
, before performing any maintenance and observe all
warnings.
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......