Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-09
207
16
16-Channel, 24 VDC Discrete Output MTA
Part No. 6ES7650-1AD11-2XX0
16.1
Description
This section contains information and requirements to facilitate installation of
Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AD11-2XX0),
designed to interface with the Siemens ET 200M 16-Channel, 24 VDC Discrete
Output module (6ES7 322-8BH10-0AB0.
16.2
Features
The following features have been incorporated into this MTA:
•
Redundant power connections
•
LED indication of redundant power supply condition
•
LED indication of reverse polarity
•
Power monitor output
•
Dual connectors for redundant I/O Module operation
•
Per module power fusing
•
Per channel LED indication of output status (ON or OFF)
•
Shield connections available for channel cabling
•
Ground stud for connecting shield to earth ground
16.3
Operation
Power is supplied via the removable power connector marked
L+A
,
MA
, and
L+B
,
MB
. Each has a green LED to indicate the presence of voltage over 15 VDC. The
case of polarity reversal of the power supply is indicated by the LEDs illuminating
red. The LEDs are marked
A POWER
and
B POWER
.
Incoming power from
A
and
B
is diode OR’d to provide the MTA and the module
power from either power source. The output from the dual diode is sent to the I/O
modules via the module power fuses.
An onboard Power Monitor System (PMS) is used to provide an isolated dry
contact when redundant power is supplied to MTAs. Only when power is supplied
to both power inputs the output contacts
1
and
2
are closed. The Power Monitor
System is designed to detect only the presence or absence of power. It is not
designed to detect supply voltage which is outside the specification threshold.
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......