6-Channel F Analog Input HART MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
132
A5E00482820-12
10.14 Input Sharing
10.14.1 Description
This section contains information and requirements for input sharing between a
Failsafe Analog Input module (6ES7 336-4GE00-0AB0) and a Standard Analog
Input Module (6ES7 331-7NF00-0AB0, E-Stand 5 or higher), using the Siemens
FAIH Marshalled Termination Assembly (MTA) (6ES7650-1AH61-5XX0 and the
Siemens AI Marshalled Termination Assembly (MTA) (6ES7650-1AA51-2XX0 or
6ES7650-1AA50-2XX0).
10.14.2 Purpose
Input sharing allows the transmitter signal to be distributed to both the Fail-Safe
Analog Input Module and the Standard Analog Input Module. Both systems will
then receive the same input data.
Figure 10–9 FAIH SAI Input Sharing
150
O
H
M
J2
+
+
CH IN
250
O
H
M
-
CURRENT
SOURCE
SAI MODULE
MANA
JUMP
E
R
J1
6.2 V
FAI MODULE
-
SAI MTA
1
5.6 V
FAIH MTA