8-Channel Analog Output MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
62
A5E00482820-12
6.3
Operation
Power is supplied via the two removable power connectors which are retained by
screws and marked
L+A
,
MA,
and
L+B
,
MB
. Each has circuitry to detect the
presence of voltage over 15 VDC and turn on the LED indicator. The LEDs are
marked
A POWER
and
B POWER
. There is also a connector (
J3
) for a Power
Monitor board used to indicate the presence of both A and B power. See Section
19,
Power Monitor Board
(6ES7650-1BA02-0XX0).
Incoming power from
A
and
B
is diode OR’d, in CR106, to provide the MTA and
the module power from either input source. The output from CR106 is sent to the
I/O modules via the module fuses. Module Fuse 1 (
F100
) supplies the I/O module
plugged into
J1
and Module Fuse 2 (
F101
) supplies power to the I/O module
plugged into J2. The channels do not require power from the I/O power supply and
therefore no channel power circuitry is required.
Field Terminals, C (
CHx+
), Channel – (
CHx-
), and Shield (
SHx
), connect
to the field devices.
CHx+
is the current output source and
CHx
- is the current
output sink. The I/O module outputs from
J1
and
J2
are diode OR’d, via CR1-
CR16, before connecting to
CHx+
of the Field terminals. Redundant operation
uses two modules with one each connected to
J1
and
J2
, while non-redundant
systems have one module connected to either
J1
or
J2
.
The field termination connector is removable for ease of wiring maintenance and is
retained by friction.
6.4
Installation Requirements
See Section 2,
, before performing any installation and observe all
warnings
A common interconnecting cable (6ES7922-3BD00-0AS0 or 6ES7922-3BJ00-
0AS0), supporting eight analog output channels, interconnects the analog output
termination assembly to the 8-channel analog output module (6ES7 332-5HF00-
0AB0, E-Stand 3 or higher). See Figure 2-11.
It may be necessary to modify the printed circuit board as follows:
To separate channel input low from power supply common, cut and remove the
jumper
W200
.
Note
To disconnect the interconnecting cable shield from ground at the MTA only, cut
and remove the shield disconnect jumper,
W100
and
W101
, for the associated
cable.
6.5
Maintenance
See Section 3,
, before performing any maintenance and observe all
warnings
Under normal operation, the
A/B
Power LED
and
Module 1/2 Fuse LED
are on. If
both are off, check the power supply to MTA. If the
A/B
Power LED
is off, check
the power supply to the MTA. If
Module 1/2 Fuse LED
is off, check the module
fuse and replace if necessary.
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......