6-Channel F Analog Input HART MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
153
11.11.5 Hardware Configuration
FAI
: Redundancy not supported. The HW configuration should be setup for Non-
redundant operation.
SAI
: The SAI MTA supports redundancy for the Standard Modules and redundant
modules can be used, as selected by the user. See section 4.10.
Addresses
FAI
: Input address and process image should be set to the user preferences.
SAI
: Input address and process image should be set to the user preferences. See
section 4.10.
Inputs
FAI
: Set to user preferences.
SAI
: Under the
Inputs
tab the
Measuring Type
should be set to
4DMU
(current)
with
Measuring Range
set to
4..20 mA
. All other settings are up to the user. See
section 4.10.
Because the FAI has only 6 inputs the SAI will only use 6 inputs for the sharing
operation. The other two inputs can be used for other analog signals.
Figure 11–8 SAI 8-Channel Analog Input Hardware Configuration: Inputs Sharing
Configuration