16-Channel, 24 VDC Discrete Output MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
209
Note
Status LED
With a normally connected load, the green Status LED is on when the channel is
switched ON, and OFF when the channel is switched off.
The green Status LED is also on when the channel is switched OFF and not
connected to the external load (wire break is indicated in module diagnostic).
The illumination of the LED in OFF-status (when the channel is not connected to
the load) can be avoided when a resistor of 10k Ohm is connected between Chx+
and Chx-. In this case the module does not provide wire break diagnostic on that
channel.