6-Channel F Analog Input HART MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
142
A5E00482820-12
11.6.1
Maintenance for 2-wire transducer supply
The power supply for 2-wire transducer is individually short circuit proofed for each
channel. In case of a external short circuit, provided by a faulty wiring, the current
is limited up to 40 mA.
The power supply circuit works in redundant mode. By this reason also in case of a
internal component error the normal current range (<24mA) will be supported.
Nevertheless a periodic check of the 2-wire power supply will be commended.
Please notice::
This check will disable the measurement on both conducted FAIH- modules.
During test both modules will provide a broken wire diagnostic.