8-Channel Analog Output MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
66
A5E00482820-12
6.10
Hardware Configuration
The Standard Analog Output MTA has no jumpers that affect the Module Hardware
Configuration; however, the MTA design restricts the Module output to the current
mode only.
Note
Redundant Operation. If a redundant Analog Output Module loses power (F10x
opens) or is removed from service, then the output current will drop to 50% of its
value for several controller cycles.
6.10.1
Addresses
Non-redundant Operation
The choice of the Input Address and Process Image are left to the user.
Redundant Operation
Process Image should be set to something other than the default. The choice of
the Input Address is left to the user.
Figure 6–3 shows an analog input configured for redundant operation.
Figure 6–3 8-Channel Analog Output Hardware Configuration: Address Setup for Redundant Operation