Installation
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
33
2.4
Removal Procedure
Should it be necessary to remove or replace a termination assembly, follow the
procedures outlined below.
2.4.1
Without Cover
Step
Action
1
Remove power and signals from the MTA
2
Remove ground connection to MTA shield stud if applied
3
Unplug the interconnecting cable into the D25 or D50 on the MTA
4
Unplug the field terminal connectors into the MTA
5
Unplug the IO power connector into the MTA
6
If the Power Monitor Board is used, remove the connection to the Power Monitor
Board or remove the Power Monitor Board for use on a replacement MTA.
7
Remove MTA from DIN rail using screwdriver to release the latch.
8
Follow the installation procedure in section 2.3 to install a replacement MTA.
2.4.2
With Cover
Refer to Figure 1.2
Step
Action
1
Remove power and signals from the MTA
2
Remove cover using screw driver to disengage the cover retaining tabs from cover.
3
Remove ground connection to MTA shield stud if applied
4
Unplug the interconnecting cable into the D25 or D50 on the MTA
5
Unplug the field terminal connectors into the MTA
6
Unplug the IO power connector into the MTA
7
Remove MTA from DIN rail using screwdrivers to release the latches. Latches are
accessed through slots in frame.
8
Follow the installation procedure in section 2.3 to install a replacement MTA.
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......